PHOENIX CONTACT MINI MCR-SL-U-I-0 MINI MCR-SL-U-I-0 2813512 PHOENIX CONTACT MCR 3-way isolating amplifier, for electrical isolation of analog .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-SL-U-I-0 2813512 PHOENIX CONTACT MCR 3-way isolating amplifier, for electrical isolation of analog ..

MINI MCR-SL-U-I-0

2813512

PHOENIX CONTACT

1 Pcs.

MCR 3-way isolating amplifier, for electrical isolation of analog signals, with screw connection, input signal: 0 V ... 10 V, output signal: 0 mA ... 20 mA

Automation > Isolation amplifier
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact MINI MCR-SL-U-I-0 isolating amplifiers provide robust galvanic isolation for standard analog voltage and current signals in industrial control panels. They prevent measurement errors caused by dangerous surges and common-mode voltage interference. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated supply voltage DC (EF007078): 19.2 V
  • Number of input ranges -60 mV ... +60 mV (EF006927): 0
  • Number of input ranges -100 mV ... +100 mV (EF006912): 0
  • Number of input ranges -300 mV ... +300 mV (EF006920): 0
  • Number of input ranges -500 mV ... +500 mV (EF006926): 0
  • Number of input ranges -1 V ... +1 V (EF006906): 0
  • Number of input ranges -2 V ... +2 V (EF006913): 0
  • Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
  • Number of input ranges -5 V ... +5 V (EF006923): 0
  • Number of input ranges -10 V ... +10 V (EF006909): 0
  • Number of input ranges -20 V ... +20 V (EF006917): 0
  • Number of input ranges 0 mV ... 60 mV (EF006905): 0
  • Number of input ranges 0 mV ... 100 mV (EF006893): 0
  • Number of input ranges 0 mV ... 200 mV (EF006898): 0
  • Number of input ranges 0 mV ... 300 mV (EF006901): 0
  • Number of input ranges 0 mV ... 500 mV (EF006904): 0

More info

▲

Product description

The 6.2 mm wide standard signal 3-way isolating amplifier MINI MCR-SL-U-I-... is used for electrical isolation, conversion, amplification and filtering of standard signals.

On the input side, 0...10 V are measured, and made available at the module output as a galvanically isolated 0...20 mA, or 4...20 mA signal.

Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.

Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Degree of protectionIP20

Input data

Number of inputs1
Configurable/programmableno
Voltage input signal0 V ... 10 V
Max. input voltage30 V
Input resistance of voltage inputapprox. 100 kΩ

Output data

Number of outputs1
Configurable/programmableno
Current output signal0 mA ... 20 mA
Max. output current28 mA
Load/output load current output≤ 500 Ω

Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption< 20 mA
Power consumption< 450 mW

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length12 mm
Screw threadM3

General

No. of channels1
Maximum transmission error≤ 0.1 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Temperature coefficient, typical< 0.002 %/K
Limit frequency (3 dB)approx. 100 Hz
Step response (10-90%)approx. 3.5 ms
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Pollution degree2
Rated insulation voltage50 V AC/DC
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
ConformanceCE-compliant
ATEXEx II 3 G Ex nA IIC T4 Gc X
UL, USA / CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5 applied for
GLGL EMC 2 D

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value5 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value5 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value5 %

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.