View larger
MINI MCR-SL-SHUNT-UI-NC 2810780 PHOENIX CONTACT Signal conditioner
MINI MCR-SL-SHUNT-UI-NC
2810780
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The MINI MCR-SL-SHUNT-UI-NC 2810780 Phoenix Contact Signal conditioner is an industrial interface module deployed in control cabinets to process, isolate, and convert sensitive instrumentation signals. Devices in this category ensure signal integrity between field sensors and controllers by filtering electrical interference and matching voltage or current levels across automation networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 19.2 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 1
- Number of input ranges -100 mV ... +100 mV (EF006912): 1
- Number of input ranges -300 mV ... +300 mV (EF006920): 1
- Number of input ranges -500 mV ... +500 mV (EF006926): 1
- Number of input ranges -1 V ... +1 V (EF006906): 1
- Number of input ranges -2 V ... +2 V (EF006913): 1
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 1
- Number of input ranges 0 mV ... 100 mV (EF006893): 1
- Number of input ranges 0 mV ... 200 mV (EF006898): 1
- Number of input ranges 0 mV ... 300 mV (EF006901): 1
- Number of input ranges 0 mV ... 500 mV (EF006904): 1
More info
▲Key Commercial Data
| Orderkey | 2810780 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 94 (C-7-2015) |
| GTIN | 4046356305341 |
| Weight per Piece (excluding packing) | 117.700 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m |
Input data
| Number of inputs | 1 |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Voltage input signal | -50 mV ... 50 mV |
| -60 mV ... 60 mV | |
| -75 mV ... 75 mV | |
| -80 mV ... 80 mV | |
| -100 mV ... 100 mV | |
| -120 mV ... 120 mV | |
| -150 mV ... 150 mV | |
| -200 mV ... 200 mV | |
| -240 mV ... 240 mV | |
| -300 mV ... 300 mV | |
| -500 mV ... 500 mV | |
| -600 mV ... 600 mV | |
| -750 mV ... 750 mV | |
| -800 mV ... 800 mV | |
| -1 V ... 1 V | |
| -1.2 V ... 1.2 V | |
| -1.5 V ... 1.5 V | |
| -2 V ... 2 V | |
| -2.4 V ... 2.4 V | |
| -3 V ... 3 V | |
| 0 mV ... 50 mV | |
| 0 mV ... 60 mV | |
| 0 mV ... 75 mV | |
| 0 mV ... 80 mV | |
| 0 mV ... 100 mV | |
| 0 mV ... 120 mV | |
| 0 mV ... 150 mV | |
| 0 mV ... 200 mV | |
| 0 mV ... 240 mV | |
| 0 mV ... 300 mV | |
| 0 mV ... 500 mV | |
| 0 mV ... 600 mV | |
| 0 mV ... 750 mV | |
| 0 mV ... 800 mV | |
| 0 V ... 1 V | |
| 0 V ... 1.2 V | |
| 0 V ... 1.5 V | |
| 0 V ... 2 V | |
| 0 V ... 2.4 V | |
| 0 V ... 3 V | |
| max. input voltage | approx. 3 V DC |
| Input resistance of voltage input | approx. 10 kΩ |
Output data
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Voltage output signal | 0 V ... 10 V |
| 2 V ... 10 V | |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| -10 V ... 10 V (The bi-polar output can be used only for bi-polar input signals.) | |
| -5 V ... 5 V (The bi-polar output can be used only for bi-polar input signals.) | |
| Current output signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | < 500 Ω (at 20 mA) |
| Ripple | < 20 mVPP(at 500 Ω) |
| < 20 mVPP(at 10 kΩ) |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 19.2 V DC ... 30 V DC |
| Max. current consumption | < 25 mA |
| Power consumption | < 450 mW (Current output) |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 12 mm |
| Screw thread | M3 |
| Connection technology | 2-wire |
General
| No. of channels | 1 |
|---|---|
| Maximum transmission error | ≤ 0.2 % |
| < 0.4 % (Without adjustment) | |
| Maximum temperature coefficient | < 0.01 %/K |
| Temperature coefficient, typical | < 0.002 %/K |
| Limit frequency (3 dB) | 100 Hz / 30 Hz switchable |
| Step response (10-90%) | 3.5 ms (At 100 Hz) |
| Electrical isolation | Basic insulation according to EN 61010 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 30 V AC |
| Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | green |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Certificate of classification | DNV GL TAA00000N1 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 6 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 6 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 6 % |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | Basic insulation according to EN 61010 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |