View larger
QUINT-ORING/24DC/2X40/1X80 2902879 PHOENIX CONTACT Redundancy module
QUINT-ORING/24DC/2X40/1X80
2902879
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection module
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A redundancy module like the Phoenix Contact QUINT-ORING/24DC/2X40/1X80 is implemented in critical power distribution systems to decouple parallel power supply units and ensure uninterrupted plant operation. Redundancy units automatically switch loads between power sources in the event of a supply failure, enhancing overall system reliability.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Voltage type (operating voltage) (EF005294): DC
- Operating voltage DC (EF008208): 18 V
- With LED indication (EF005950): Yes
More info
▲Key Commercial Data
| Orderkey | 2902879 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 261 (C-4-2017) |
| GTIN | 4046356698276 |
| Weight per Piece (excluding packing) | 900.000 g |
| Custom tariff number | 85049091 |
| Country of origin | CN (China) |
Dimensions
| Width | 66 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Width with alternative assembly | 122 mm |
| Height with alternative assembly | 130 mm |
| Depth with alternative assembly | 69 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K) |
| Ambient temperature (start-up type tested) | -40 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Degree of pollution | 2 |
| Installation height | 2000 m |
| 2000 m |
Input data
| Nominal input voltage range | 24 V DC |
|---|---|
| Input voltage range | 18 V DC ... 28 V DC (SELV) |
| Nominal input current | 2x 40 A (-25 °C ... 60 °C) |
| 1x 80 A (-25 °C ... 60 °C) | |
| Maximum input current | 2x 45 A (-25°C ... 40°C) |
| 1x 90 A (-25°C ... 40°C) | |
| 215 A (12 ms, SFB Technology) |
Output data
| Nominal output voltage | 0.2 V (< DC input) |
|---|---|
| 24 V DC | |
| Nominal output current (IN) | 80 A (Increasing power) |
| 40 A (Redundancy) | |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| Connection in series | No |
| Output overvoltage protection | ≤ 32 V DC |
| Power loss nominal load max. | 16 W (IOUT= 80 A) |
General
| Net weight | 0.9 kg |
|---|---|
| Efficiency | > 98 % |
| Protection class | III |
| Degree of protection | IP20 |
| MTBF (IEC 61709, SN 29500) | |
| > 720000 h (40 °C) | |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Assembly instructions | alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 35 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 35 mm² |
| Conductor cross section AWG min. | 2 |
| Stripping length | 18 mm |
| Screw thread | M5 |
Connection data for signaling
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 16 |
| Conductor cross section AWG max. | 10 |
| Stripping length | 10 mm |
| Screw thread | M3 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2:2005 |
| Connection in acc. with standard | CUL |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m (Test Level 3) |
| Frequency range | 1.4 GHz ... 2 GHz |
| Test field strength | 3 V/m (Test Level 2) |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-6-3 |
| EN 61000-4-6 | |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V (Test Level 3) |
| Low Voltage Directive | Conformance with LV directive 2006/95/EC |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
| UL approvals | UL/C-UL listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 25; |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |