Protection against damaging voltage surges on data and signal lines is provided by the Phoenix Contact DT-UFB-485/BS surge protection device. These modules are routinely deployed in industrial automation setups to secure serial communication buses and sensitive interface electronics against transient electrical disturbances. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2920612
- Packing unit: 1 pc
- Catalog page: Page 147 (C-4-2017)
- GTIN: 4046356155120
- Weight per Piece (excluding packing): 305.200 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 108 mm
- Width: 25 mm
- Depth: 63 mm
- Ambient temperature (operation): -40 °C ... 85 °C
- Degree of protection: IP20
- Housing material: Zinc die-cast
- Color: silver/black
- Standards for cearances and creepage distances: IEC 60664-1
- Mounting type: Connection-specific attachment plug and DIN rail, 35 mm
More info
▲Key Commercial Data
| Orderkey | 2920612 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 147 (C-4-2017) |
| GTIN | 4046356155120 |
| Weight per Piece (excluding packing) | 305.200 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | Zinc die-cast |
|---|---|
| Color | silver/black |
| Standards for cearances and creepage distances | IEC 60664-1 |
| VDE 0110-1 | |
| Mounting type | Connection-specific attachment plug and DIN rail, 35 mm |
| Type | Attachment plug for DIN rail mounting |
| Number of positions | 5 |
| Direction of action | Line-Line & Line-Ground/Shield |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | B2 |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Maximum continuous voltage UC | 12 V DC |
| Rated current | ≤ 380 mA (25 °C) |
| Operating effective current ICat UC | ≤ 1 µA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-line) | ≤ 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | ≤ 5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 25 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 25 V |
| Residual voltage at In(line-line) | ≤ 25 V |
| Residual voltage at In(line-earth) | ≤ 55 V |
| Residual voltage at In(line-signalground) | ≤ 25 V |
| Voltage protection level Up(line-line) | ≤ 30 V (B2 - 100 A) |
| ≤ 30 V (C1 - 500 A) | |
| ≤ 40 V (C2 - 5 kA) | |
| Voltage protection level Up(line-earth) | ≤ 700 V (B2 - 100 A) |
| ≤ 700 V (C1 - 500 A) | |
| ≤ 750 V (C2 - 5 kA) | |
| Response time tA(line-line) | ≤ 100 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 30 MHz) |
| typ. 0.3 dB (≤ 7 MHz / 150 Ω) | |
| typ. 0.3 dB (≤ 2 MHz / 600 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 50 MHz |
| Resistance in series | 3.3 Ω 10 % |
| Surge protection fault message | none |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| B2 - 4 kV/100 A | |
| Impulse durability (line-earth) | B2 - 4 kV/100 A |
| C1 - 1 kV/500 A | |
| C2 - 10 kV/5 kA | |
| D1 - 1 kA |
Connection data
| Connection method | D-SUB-9 |
|---|---|
| Connection method IN | D-SUB-9 socket |
| Connection method OUT | D-SUB-9 connector |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| DIN EN 61643-21 | |
| Standards/specifications | DIN EN 61643-21 2002 |