View larger
MINI MCR-2-I4-U 2902002 PHOENIX CONTACT Signal conditioner
MINI MCR-2-I4-U
2902002
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Industrial control loops use signal conditioner units like the Phoenix Contact MINI MCR-2-I4-U to convert, filter, and isolate analog process signals between field sensors and control systems. This hardware protects sensitive automation electronics from electrical interference, ground loops, and voltage surges while ensuring accurate measurement transmission.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 9.6 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
More info
▲Key Commercial Data
| Orderkey | 2902002 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 74 (C-5-2017) |
| GTIN | 4046356651844 |
| Weight per Piece (excluding packing) | 104.400 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Input data
| Number of inputs | 1 |
|---|---|
| Configurable/programmable | no |
| Current input signal | 4 mA ... 20 mA |
| Input resistance current input | approx. 63 Ω (+ 0.7 V for test diode) |
Output data
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | no |
| Voltage output signal | 0 V ... 10 V |
| Max. output voltage | 11 V |
| Short-circuit current | < 15 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Ripple | < 20 mVPP(at 10 kΩ) |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
| Typical current consumption | 25 mA (24 V DC) |
| 54 mA (12 V DC) | |
| Power consumption | ≤ 200 mW (at 9.6 V DC) |
Connection data
| Connection method | Screw connection |
|---|---|
| Single conductor/terminal point, solid, with ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, with ferrule, max. | 1.5 mm² |
| Single conductor/terminal point, solid, without ferrule, min. | 0.2 mm² |
| Single conductor/terminal point, solid, without ferrule, max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Min. AWG conductor cross section, flexible | 24 |
| Max. AWG conductor cross section, flexible | 12 |
| Stripping length | 10 mm |
| Screw thread | M3 |
General
| No. of channels | 1 |
|---|---|
| Maximum transmission error | 0.1 % (of final value) |
| Maximum temperature coefficient | 0.01 %/K |
| Temperature coefficient, typical | 0.01 %/K |
| Limit frequency (3 dB) | approx. 30 Hz |
| Step response (10-90%) | approx. 10 ms |
| Protective circuit | Transient protection |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Overvoltage category | II |
| Degree of pollution | 2 |
| Rated insulation voltage | 300 V (effective) |
| Test voltage, input/output/supply | 3 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | gray |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| Certificate of classification | DNV GL 14445-15HH |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Standards/regulations | EN 61000-4-2 |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA IIC T4 Gc X |
| UL, USA/Canada | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T6 | |
| Class I, Zone 2, Group IIC T6 | |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |