View larger
MINI MCR-2-RPSS-I-I 2902014 PHOENIX CONTACT Repeater power supply
MINI MCR-2-RPSS-I-I
2902014
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Supplying power to 2-wire transmitters while simultaneously transmitting the analog 4-20 mA current signal is the primary function of a Phoenix Contact MINI MCR-2-RPSS-I-I repeater power supply. Such devices are deployed extensively in process measurement loops to ensure transparent signal transmission and electrical decoupling between field instrumentation and control hardware.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
- Product type: Repeater power supply
- Product family: MINI Analog Pro
- No. of channels: 1
- Type: Signal conditioner
- Data management status Article revision: 12
- Insulation characteristics: GB Standard Overvoltage category: II
- Pollution degree: 2
- Electrical isolation: 3-way isolation
- Electrical isolation between input and output: yes
- Limit frequency (3 dB): > 1.75 kHz
- Protective circuit: Transient protection
- Signal transmission behavior: In = Out
- Step response (10-90%): < 200 µs (typ.)
- Maximum temperature coefficient: 0.0075 %/K
- Temperature coefficient, typical: 0.0075 %/K
More info
▲| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Product type | Repeater power supply |
| Product family | MINI Analog Pro |
| No. of channels | 1 |
| Type | Signal conditioner |
| Data management status | |
| Article revision | 12 |
| Insulation characteristics: GB Standard | |
| Overvoltage category | II |
| Pollution degree | 2 |
| Electrical isolation | 3-way isolation |
| Electrical isolation between input and output | yes |
| Limit frequency (3 dB) | > 1.75 kHz |
| Protective circuit | Transient protection |
| Signal transmission behavior | In = Out |
| Step response (10-90%) | < 200 µs (typ.) |
| Maximum temperature coefficient | 0.0075 %/K |
| Temperature coefficient, typical | 0.0075 %/K |
| Maximum transmission error | 0.05 % (of final value in repeater power supply operation) |
| 0.1 % (of final value in isolator operation) | |
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 300 Vrms |
| Test voltage | 3 kV AC (50 Hz, 60 s) |
| Insulation | Reinforced insulation according to IEC/EN 61010-1 |
| Supply | |
| Nominal supply voltage | 24 V DC |
| Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
| Typical current consumption | 25 mA (at 24 V DC and in isolator operation) |
| 50 mA (at 24 V DC and in repeater power supply operation) | |
| 55 mA (at 12 V DC and in isolator operation) | |
| 110 mA (at 12 V DC and in repeater power supply operation) | |
| Power consumption | ≤ 1400 mW (at IOUT= 20 mA, 9.6 V DC, 600 Ω load) |
| Signal: Current | |
| Description of the input | Sensor circuit |
| Number of inputs | 1 |
| Current input signal | 0 mA ... 20 mA (isolator operation) |
| 4 mA ... 20 mA (repeater power supply and isolator operation) | |
| Input resistance current input | 68 Ω (+0.7 V for test diode) |
| Transmitter supply voltage | > 19.5 V |
| Signal: Current | |
| Number of outputs | 1 |
| Non-load voltage | < 20 V |
| Current output signal | 0 mA ... 20 mA (isolator operation) |
| 4 mA ... 20 mA (repeater power supply and isolator operation) | |
| Max. current output signal | 24 mA |
| Load/output load current output | ≤ 600 Ω (20 mA) |
| Ripple | < 20 mVPP(600 Ω) |
| Connection method | Screw connection |
| Stripping length | 10 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² (with ferrule) |
| 0.14 mm² ... 2.5 mm² (without ferrule) | |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 (flexible) |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Ex installation (EPL) | Gc |
| Div. 2 |
| Data communication (bypass) | |
| HART function | Yes |
| Limit frequency (3 dB) | 1.75 kHz |
| Status display | Green LED (supply voltage) |
| Width | 6.2 mm |
| Height | 109.81 mm |
| Depth | 119.2 mm |
| Color | gray (RAL 7042) |
| Housing material | PBT |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| CE | |
| Certificate | CE-compliant |
| ATEX | |
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | BVS 19 ATEX E 047 X |
| UKCA Ex (UKEX) | |
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | PxCIF21UKEX2902000X |
| IECEx | |
| Identification | Ex ec IIC T4 Gc |
| Certificate | IECEx BVS 19.0041X |
| CCC / China-Ex | |
| Identification | Ex nA IIC T4 Gc |
| UL, USA/Canada | |
| Identification | UL 508 Listed |
| Class I, Div. 2, Groups A, B, C, D T5 | |
| Class I, Zone 2, Group IIC T5 | |
| Shipbuilding approval | |
| Certificate | DNV GL TAA00002UA |
| EAC Ex | |
| Identification | 2Ex ec IIC T4 Gc |
| Certificate | BY/112 02.01 TP012 103.01 00079 |
| DNV GL data | |
| Temperature | B |
| Humidity | B |
| Vibration | A |
| EMC | A |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Noise emission | EN 61000-6-4 |
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 |
| Electrostatic discharge | |
| Comments | Safety measures must be taken to prevent electrostatic discharge. |
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
| Fast transients (burst) | |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 |
| Conducted interference | |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Electrical isolation | 3-way isolation |
| GB Standard | |
| Standards/regulations | GB 3836.1 |
| GB 3836.8 | |
| Mounting type | DIN rail mounting |
| Assembly note | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
| Mounting position | any |