View larger
MINI MCR-SL-UI-UI-NC 2864150 PHOENIX CONTACT 3-way isolating amplifier for the electrical isolation of analo..
MINI MCR-SL-UI-UI-NC
2864150
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Bridging measurement equipment and control systems, the Phoenix Contact MINI MCR-SL-UI-UI-NC serves as a 3-way isolating amplifier for the electrical isolation of analog signals. Isolating amplifiers prevent ground loops and protect sensitive instrumentation by providing secure galvanic separation between input, output, and power supply circuits. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 19.2 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
More info
▲Dimensions
| Width | 6.2 mm |
|---|---|
| Height | 93.1 mm |
| Depth | 102.5 mm |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Degree of protection | IP20 |
Input data
| Number of inputs | 1 |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Voltage input signal | 0 V ... 10 V |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| 2 V ... 10 V | |
| Current input signal | 0 mA ... 20 mA |
| 4 mA ... 20 mA | |
| Max. input voltage | 30 V |
| Max. input current | 50 mA |
| Input resistance of voltage input | approx. 100 kΩ |
| Input resistance current input | approx. 50 Ω |
Output data
| Number of outputs | 1 |
|---|---|
| Configurable/programmable | Yes, unconfigured |
| Voltage output signal | 0 V ... 10 V |
| 0 V ... 5 V | |
| 1 V ... 5 V | |
| 2 V ... 10 V | |
| Current output signal | 0 mA ... 20 mA (please indicate if different setting when ordering) |
| 4 mA ... 20 mA | |
| Max. output voltage | approx. 12.5 V |
| Max. output current | 28 mA |
| Short-circuit current | approx. 22 mA |
| Load/output load voltage output | ≥ 10 kΩ |
| Load/output load current output | < 500 Ω (at 20 mA) |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
| Max. current consumption | < 19 mA (Current output, at 24 V DC incl. load) |
| < 9 mA (Voltage output, at 24 V DC incl. load) | |
| Power consumption | < 450 mW (Current output) |
| < 200 mW (Voltage output) |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Stripping length | 12 mm |
| Screw thread | M3 |
General
| No. of channels | 1 |
|---|---|
| Maximum transmission error | ≤ 0.1 % (of final value) |
| < 0.4 % (Without adjustment) | |
| Maximum temperature coefficient | < 0.01 %/K |
| Temperature coefficient, typical | < 0.002 %/K |
| Limit frequency (3 dB) | approx. 100 Hz |
| Step response (10-90%) | approx. 3.2 ms |
| Protective circuit | Transient protection |
| Electrical isolation | Basic insulation according to EN 61010 |
| Overvoltage category | II |
| Pollution degree | 2 |
| Rated insulation voltage | 50 V AC/DC |
| Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Color | green |
| Housing material | PBT |
| Mounting position | any |
| Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Conformance | CE-compliant |
| ATEX | Ex II 3 G Ex nA IIC T4 Gc X |
| UL, USA / Canada | UL 508 Recognized |
| Class I, Div. 2, Groups A, B, C, D T5 | |
| GL | GL EMC 2 D |
EMC data
| Designation | Electromagnetic RF field |
|---|---|
| Standards/regulations | EN 61000-4-3 |
| Typical deviation from the measuring range final value | 5 % |
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
| Typical deviation from the measuring range final value | 5 % |
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
| Typical deviation from the measuring range final value | 5 % |