PHOENIX CONTACT D-LAN-19"-24 D-LAN-19"-24 2838791 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

D-LAN-19"-24 2838791 PHOENIX CONTACT Surge protection device

D-LAN-19"-24

2838791

PHOENIX CONTACT

1 Pcs.

Surge protection device 19" rack with 24 surge-protected ports for data interfaces in Ethernet networks (1000Base-T), Token ring, FDDI/CDDI according to Class D/EN 50173 (CAT5e), connection in the protection module: RJ45 females.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Designed for rack-mounted network applications, the Phoenix Contact D-LAN-19"-24 surge protection device shields Ethernet and data communication hardware from transient surges. Rack-mounted suppression units are routinely deployed in server rooms and industrial control hubs to protect sensitive networking switches from lightning-induced overvoltages. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2838791
  • Packing unit: 1 pc
  • Note: Made to Order (non-returnable)
  • Catalog page: Page 143 (C-4-2017)
  • GTIN: 4017918959968
  • Weight per Piece (excluding packing): 3,091.000 g
  • Custom tariff number: 85363010
  • Country of origin: DE (Germany)
  • Height: 44 mm
  • Width: 483 mm
  • Depth: 160 mm
  • Height unit: 1 U
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Degree of protection: IP20
  • Housing material: Sheet steel
  • Color: beige

More info

▲

Key Commercial Data

Orderkey2838791
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 143 (C-4-2017)
GTIN4017918959968
Weight per Piece (excluding packing)3,091.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height44 mm
Width483 mm
Depth160 mm
Height unit1 U

Ambient conditions

Ambient temperature (operation)-40 °C ... 80 °C
Degree of protectionIP20

General

Housing materialSheet steel
Colorbeige
Standards for cearances and creepage distancesDIN VDE 0110-1
IEC 60664-1
Overvoltage categoryII
Degree of pollution2
Mounting type19" rack
Type19" rack patch module
Number of positions24
Direction of actionLine-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
B3
Maximum continuous voltage UC6 V DC
Rated current1.5 A (25 °C)
Operating effective current ICat UC≤ 1 mA
Residual current IPE≤ 1 mA (jumper 2 unplugged)
Nominal discharge current In(8/20) µs (line-line)350 A
Nominal discharge current In(8/20) µs (line-earth)350 A
Nominal discharge current In(8/20) µs (shield-earth)2.5 kA (with insulated housing)
Total discharge current Itotal(8/20) µs10 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)
Nominal pulse current Ian (10/1000) µs (line-line)100 A
Nominal pulse current Ian (10/1000) µs (line-earth)100 A
Output voltage limitation at 1 kV/µs (line-line) static≤ 20 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 30 V (J2 plugged)
≤ 170 V (J2 unplugged)
Output voltage limitation at 1 kV/µs (shield-earth) static≤ 700 V (with insulated shield)
Residual voltage at In(line-line)≤ 65 V
Residual voltage at In(line-earth)≤ 45 V (J2 ON)
≤ 220 V (J2 OFF)
Residual voltage at In(shield-earth)≤ 700 V
Voltage protection level Up(line-line)≤ 50 V (C1 - 500 V / 250 A)
Voltage protection level Up(line-earth)≤ 40 V (C1 - 500 V / 250 A (J2 ON))
≤ 180 V (C1 - 500 V / 250 A (J2 OFF))
Voltage protection level Up(shield-ground)≤ 800 V (with insulated housing)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 1 ns
Response time tA (line-shield)≤ 100 ns
Input attenuation aE, sym.typ. 1 dB (≤ 100 MHz)
Input attenuation aE, asym.
Near-end crosstalk attenuationtyp. 36 dB (100 Ω system / 100 MHz)
Cut-off frequency fg (3 dB), sym. in 100 Ohm system> 100 MHz
Capacity (line-line)typ. 20 pF
Capacity (line-earth)typ. 1 pF
Surge protection fault messagenone
Impulse durability (line-line)C1 - 500 V / 250 A
Impulse durability (line-earth)C1 - 500 V / 250 A
Impulse durability (shield-earth)C2 (4 kV / 2 kA)

Connection data

Connection methodRJ45
Connection method INRJ45 socket
Connection method OUTRJ45 socket
Connection technologyNetwork interfaces (e.g. Ethernet, Token Ring and CDDI/FDDI)

Standards and Regulations

Standards/regulationsIEC 61643-21
DIN EN 50173-1
Standards/specificationsIEC 61643-21 2000

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet