Request QuoteProduct Overview
A Phoenix Contact plug-in miniature relay with mechanical switching position acts as an electromechanical switching device used to isolate electrical circuits and route control commands safely. These components are typically installed within industrial control panels to manage high-capacity loads and provide clear visual status indication during machine operation.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- General: The outputs are not suitable for connecting different phases.
- Product Type: Individual relay
- Product Family: ESSENTIAL edition
- Operating Mode: Working time 100%
- Mechanical service life: approx. 3x 10 7 operations
- Relay Type: Electromechanical relay
- Surge Category: Ii
- Degree of pollution: 3
- Maximum Dissipated Power with Nominal Condition: 1 W
- Test Voltage (Winding/Contact): 5 kV Eff (50 Hz, 1 min., winding/contact)
- Test Voltage (Commutator/Commutator): 3 kV Eff (50 Hz, 1 min., switch/switch)
- Test Voltage (): 1 kV Eff (50 Hz, 1 min., open contact)
- Dimensioning Transient Voltage: 2.5 kV
- Arousal Side Nominal Input Voltage U N: 230 V AC
- Input Voltage Range: 184 V AC ... 253 V AC
- Mains Frequency: 50/60 Hz
More info
▲| General | They should not be used to separate SELV/PELV electrical circuits from other electrical circuits, as safe separation is not guaranteed. (valid for optocoupler variants) |
| General | The outputs are not suitable for connecting different phases. |
| General | Protection against accidental contact of the article (with voltages > 25 V AC/60 V DC) must be ensured by the system manufacturer. This is an assembly device without protection against direct contact. |
| Product Type | Individual relay |
| Product Family | ESSENTIAL edition |
| Operating Mode | Working time 100% |
| Mechanical service life | approx. 3x 107operations |
| Relay Type | Electromechanical relay |
| Insulation Properties: Leak Lines and Air Gaps Between Circuits | |
| Isolation | Basic Insulation |
| Surge Category | Ii |
| Degree of pollution | 3 |
| Maximum Dissipated Power with Nominal Condition | 1 W |
| Test Voltage (Winding/Contact) | 5 kVEff(50 Hz, 1 min., winding/contact) |
| Test Voltage (Commutator/Commutator) | 3 kVEff(50 Hz, 1 min., switch/switch) |
| Test Voltage () | 1 kVEff(50 Hz, 1 min., open contact) |
| Creepage lines and air gaps between circuits | |
| Sizing Insulation Voltage | 250 V AC |
| Dimensioning Transient Voltage | 2.5 kV |
| Arousal Side | |
| Nominal Input Voltage UN | 230 V AC |
| Input Voltage Range | 184 V AC ... 253 V AC |
| Mains Frequency | 50/60 Hz |
| Drive switching behavior | monostable |
| Drive (polarity) | bipolar |
| Typical Input Current to UN | 4.5 mA (50 Hz) |
| Input Dissipated Power with UN | 1 W |
| Typical Reaction Time | 2 ms ... 15 ms |
| Typical Open Time Range | 5 ms ... 20 ms |
| Protection Circuit | RC Module |
| Status Indication | Yellow LED |
| Coil Resistance | 24100 Ω ±10 % |
| Commute | |
| Contact Switching Type | 2 switched contacts |
| Switching Contact Type | Simple Contact |
| Contact Material | AgSnO |
| Maximum Switching Voltage | 250 V AC/DC |
| Minimum Activation Voltage | 5 V (10 mA) |
| Constant Current Limit | 8 A |
| Maximum connection current | 16 A (20 ms, open contact) |
| Minimum Shut-Off Current | 10 mA (5 V) |
| Maximum Breaking Power (Ohmic Load) | 192 W (24 V DC) |
| 240 W (30 V DC) | |
| 2000 VA (250 V AC) | |
| Connection type | FASTON Connection |
| Width | 13 mm |
| Height | 31.1 mm |
| Depth | 34 mm |
| Environmental conditions | |
| Protection Index (Relay) | RT II (Relay) |
| Protection Index (Installation Location) | IP54 (Mounting Location) |
| Ambient Temperature (Service) | -40 °C ... 70 °C |
| Ambient Temperature (Storage/Transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| Standards/Specifications | IEC 61810-1 |
| IEC 60664-1 | |
| Creepage lines and air gaps between circuits | |
| Standards/Specifications | IEC 60664-1 |
| Position for mounting | discretionary |