OMRON CS1W-PTS55 CS1W-PTS55 CS1W0300R CS1WPTS55 OMRON Module 8 Inputs Thermocouple galvanic Isolation View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CS1W-PTS55 CS1W0300R CS1WPTS55 OMRON Module 8 Inputs Thermocouple galvanic Isolation

CS1W-PTS55

CS1W0300R

CS1WPTS55

OMRON

1 Pcs.

Module 8 Inputs Thermocouple galvanic Isolation

Automation > PLC analogue I/O-module
CS1

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Omron module provides specialized signal conditioning and galvanic isolation for multi-channel sensor networks in complex industrial environments. These expansion cards safely interface delicate temperature and process measuring devices with programmable controllers while protecting internal circuitry from electrical noise. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • 4: Analog input
  • 8: Analog input
  • 16: Analog input
  • 4: Analog output
  • 8: Voltage output
  • 8: Current output
  • 4 + 4: Analog in + output
  • 4: Process input
  • 8: Process input
  • 4: Thermocouple input
  • 4: Resistance thermometer input
  • 4: Thermocouple input
  • 4: Resistance thermometer input
  • 8: Thermocouple input
  • 8: Resistance thermometer input
  • 4: 2-Wire transmitter input

More info

▲

Specifications & ordering info

Ordering information

Points

Type

Ranges

Resolution

Accuracy1

Conversion
time

Remarks

Connection type

Order code

4

Analog input

0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA

1/8,000

V: 0.2% of PV
I: 0.4% of PV

250 µs/point

Offset/gain adjustment, peak hold,
moving average, alarms

M3

CS1W-AD041-V1

8

Analog input

M3

CS1W-AD081-V1

16

Analog input

0.2% of PV

2 × MIL (34p.)

CS1W-AD161

4

Analog output

0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA

1/4,000

V: 0.3% of PV
I: 0.5% of PV

1 ms/point

Offset/gain adjustment

M3

CS1W-DA041

8

Voltage output

0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V

0.3% of PV

Offset/gain adjustment, output hold

M3

CS1W-DA08V

8

Current output

4 to 20 mA

0.5% of PV

M3

CS1W-DA08C

4 + 4

Analog in + output

0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V
(4 to 20 mA input)

1/8,000

V in: 0.2% of PV
I in: 0.4% of PV
out: 0.3% of PV

1 ms/point

Offset/gain adjustment, scaling, peak hold, moving average, alarms, output hold

M3

CS1W-MAD44

4

Process input

4 to 20 mA,
0 to 20 mA,
0 to 10 V,
-10 to 10 V,
0 to 5 V,
-5 to 5 V,
1 to 5 V,
1 to 1.25 V,
-1.25 to 1.25 V

1/64,000

0.05% of PV

5 ms/point

Configurable alarms, maintenance
functions, user-defined scaling, zero/span adjustment, square root, totaliser.

M3

CS1W-PDC11

8

Process input

-10 to 10 V,
0 to 5 V,
1 to 5 V,
4 to 20 mA

1/16,000

0.3% of PV

62.5 ms/point

Configurable alarms, zero/span adjustment, square root

M3

CS1W-PDC55

4

Thermocouple input

B, E, J, K, L, N, R, S, T,
U, WRe5-26, PLII,
-100 to 100 mV

1/64,000

0.05% of PV

5 ms/point

Configurable alarms (absolute +
rate-of-change), peak hold,
maintenance functions

M3

CS1W-PTS11

4

Resistance thermometer input

Pt50, Pt100 JPt100, Ni508.4

1/64,000

0.05% of PV

5 ms/point

Configurable alarms (absolute +
rate-of-change), peak hold,
maintenance functions

M3

CS1W-PTS12

4

Thermocouple input

B, J, K, L, R, S, T

0.1°C

0.3% of PV

62.5 ms/point

4 configurable alarm outputs

M3

CS1W-PTS51

4

Resistance thermometer input

Pt100, JPt100

0.1°C

0.3% of PV

62.5 ms/point

4 configurable alarm outputs

M3

CS1W-PTS52

8

Thermocouple input

B, J, K, L, R,S, T

0.1°C

0.3% of PV

31.2 ms/point

Configurable alarms per channel

M3

CS1W-PTS55

8

Resistance thermometer input

Pt100, JPt100

0.1°C

0.3% of PV

31.2 ms/point

Configurable alarms per channel

M3

CS1W-PTS56

4

2-Wire transmitter input

1 to 5 V,
4 to 20 mA

1/4,096

0.2% of FS

25 ms/point

Built-in power supply for transmitter, configurable alarms, square root,
rate-of-change, etc.

M3

CS1W-PTW01

8

Power transducer input

-1 to 1 mA,
0 to 1 mA

1/4,096

0.2% of FS

25 ms/point

Inrush current limiter, configurable alarms, averaging, etc.

M3

CS1W-PTR01

8

Power transducer input

-100 to 100 mV,
0 to 100 mV

1/4,096

0.2% of FS

25 ms/point

Inrush current limiter, configurable alarms, averaging, etc.

M3

CS1W-PTR02

4

Pulse rate input

20000 pps, voltage,
open collector, contact

up to
1/32,000

-

25 ms/point

Averaging, totaliser

M3

CS1W-PPS01

4

Isolated control output

1 to 5 V,
4 to 20 mA

1/4,000

I: 0.1% of FS
V: 0.2% of FS

25 ms/point

Output readback, high/low/rate limiting, disconnection alarm, zero/span
adjustment

M3

CS1W-PMV01

4

Isolated control output

-10 to 10 V,
0 to 10 V,
-5 to 5 V,
0 to 5 V,
-1 to 1 V,
0 to 1 V

1/4,000

0.1% of FS

10 ms/point

High/low/rate limiting, output hold,
zero/span adjustment

M3

CS1W-PMV02

Note: All analog I/O units are designated as special I/O units


1.Accuracy for Voltage and Current Inputs/Outputs as percentage of full scale and typical value at 25°C ambient temperature (Consult the operation manual for details)
Accuracy for Temperature Inputs/Outputs as percentage of process value and typical value at 25°C ambient temperature (Consult the operation manual for details)


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.