View larger
61F-GP-N8D 230VAC 151827 61FGPN8D230AC OMRON 8 pins General ON/OFF 220VAC,Low sensibilid
61F-GP-N8D 230VAC
151827
61FGPN8D230AC
OMRON
1 Pcs.
Automation > (Fill) level monitoring relay
Monitoring Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Omron 61F-GP-N8D 230VAC is a floatless level switch utilized for automatic water supply and drainage control in commercial and industrial liquid management systems. Level switches of this type use conductive electrodes to sense liquid presence, eliminating mechanical floats and ensuring dependable on/off switching. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Ordinary purified water or sewage water: General purpose type
- 4 km 1: 61F-GP-N8L 230AC 4KM
- 61F-GP-N8R 110AC 61F-GP-N8R 230AC DIN-rail mounting socket: PF083A-E
- Back-connecting socket: PL08
- Electrode separators: Number of electrodes
- 3: F03-14 3P
- Electrodes, connecting, and lock nuts Applicable liquids: Material
- Purified city water, industrial water, sewage: Equivalent to SUS 304 (AISI-304)
- Connecting nut: −
- Lock nut: −
- Supply voltage: 24, 100, 110, 120, 200, 220, 230 or 240 VAC
- 50/60 Hz:
- Operating voltage range: 85 to 110% of rated voltage
- Interelectrode voltage: 8 VAC
- Interelectrode current: Approx. 1 mA AC max.
More info
▲Compact plug-in (8-pin) level controller
The 61F-GP-N8 can be used for single- or two-point level control of conductive materials, both liquids and solids. These products are equipped with a red LED operation indicator.
- Low-voltage (AC) electrodes (8VAC or 24VAC)
- Operation range: 4-15kΩ, 70-300kΩ
- Detection method: conductive
- Probes need to be ordered separately
- Conforms to EMC and LVD directives, UL/CSA approved
Ordering information
Ordinary purified water, where the distance between sewage pumps and water tanks or | 2 km1 | ||
4 km1 | |||
Liquids with high specific resistance such as distilled water | |||
Liquids with low specific resistance such as salt water, sewage water, acid chemicals, | |||
Ordinary purified or sewage water, with two-wired-type electrode holder | |||
Accessories
Specifications
1 A, 250 VAC (inductive load: cosφ = 0.4), 3 A, 250 VAC (resistive load) | |||||
Electrical: 100,000 operations min., mechanical: 5,000,000 operations min | |||||