View larger
V10-C 0-320
5093404
OBO BETTERMANN
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Arrester surge current (8/20 µs) [total] | 10 kA |
|---|---|
| Blow-out | no |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,2403 kg CO2e / 1 Piece |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 35 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 2,5 mm² |
| Dimension | 320V |
| Installation type | On basic element |
| Lightning protection zone LPZ | 1→3 |
| Max. mains-side overcurrent protection | 125 |
| Maximum back-up fuse | 125 A |
| Maximum continuous voltage AC | 320 V |
| Maximum discharge current (8/20 μs) | 20 kA |
| Network form | Other |
| Nominal discharge current (8/20 µs) | 10 kA |
| Nominal voltage AC (50/60 Hz) | 320 V |
|---|---|
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Pole version | 1 |
| Protection level [L-N] | ≤1,6 |
| Protection rating | IP20 |
| Remote signalling | no |
| Response time | <25 ns |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 2+3 |
| SPD to IEC 61643-1 | Class II+III |
| Version for | 1-pole |
| Feature Name | Feature Value |
|---|---|
| Nominal discharge surge current (8/20) (EF004214) | 10 kA |
| Max. discharge surge current (8/20) (EF012274) | 20 kA |
| Nominal voltage AC (EF004220) | 320 V |
| Max. continuous voltage AC (EF004198) | 320 V |
| Voltage protection level (EF003525) | 1.2 kV |
| Voltage protection level L-N (EF004236) | 1.6 kV |
| Mounting method (EF000003) | On basic element |
| Construction size (EF002566) | 1 modular spacing |
| Max. conductor cross section solid (solid, stranded) (EF008827) | 35 mm² |
| Signalling at the device (EF004241) | Optic |
| Degree of protection (IP) (EF005474) | IP20 |