OBO BETTERMANN VF48-AC/DC-FS VF48-AC/DC-FS 5097822 OBO BETTERMANN Lightning barrier with remote signalling, 48V AC, View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VF48-AC/DC-FS 5097822 OBO BETTERMANN Lightning barrier with remote signalling, 48V AC,

VF48-AC/DC-FS

5097822

OBO BETTERMANN

1 Pcs.

Lightning barrier with remote signalling, 48V AC, MCR protection for 2-pole power supply with remote signalling, 48 V AC/DC. Surge protection/fine power protection, type 3, to EN 61643-11 with remote signalling • With remote signalling, potential-free changeover contact, for function monitoring • Suitable for DC and AC systems • With visual function display • With easy mounting, screwless connection terminals • In space-saving 17.5 mm grid • Y circuit Application: Universal use on 35 mm DIN profile rails in any standard distributor housing.

Automation > Surge protection device for terminal equipment
Surge , arrestor, type 3

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Obo Bettermann lightning barrier with remote signalling provides surge suppression for AC and DC supply lines while incorporating auxiliary changeover contacts for remote status monitoring. This dual-function capability allows system operators to track device health from central control stations.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Blow-out: no
  • CO2 Footprint (GWP) Cradle-to-Gate: 0,6888 kg CO2e / 1 Piece
  • Conductor cross-section, rigid (single-wire/multiwire), max.: 2,5 mm²
  • Conductor cross-section, rigid (single-wire/multiwire), min.: 0,14 mm²
  • Dimension: 48V AC
  • FM contacts: Changeover
  • Installation type: DIN rail 35 mm
  • Lightning protection zone LPZ: 2→3
  • Maximum continuous voltage AC: 60 V
  • Maximum continuous voltage DC: 80 V
  • Maximum discharge current (8/20 μs): 2 kA
  • Nominal discharge current (8/20 µs): 0,7 kA
  • Nominal voltage AC (50/60 Hz): 48 V
  • OBO_Nominal load current (input/output terminal): 20 A
  • Operating temperature, max.: 80 °C
  • Operating temperature, min.: -40 °C

More info

▲
Blow-outno
CO2 Footprint (GWP) Cradle-to-Gate0,6888 kg CO2e / 1 Piece
Conductor cross-section, rigid (single-wire/multiwire), max.2,5 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.0,14 mm²
Dimension48V AC
FM contactsChangeover
Installation typeDIN rail 35 mm
Lightning protection zone LPZ2→3
Maximum continuous voltage AC60 V
Maximum continuous voltage DC80 V
Maximum discharge current (8/20 μs)2 kA
Network formOther
Nominal discharge current (8/20 µs)0,7 kA
Nominal voltage AC (50/60 Hz)48 V
OBO_Nominal load current (input/output terminal)20 A
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Pole number3
Pole version2
Protection level wire-earth<1200 V
Protection level wire-wire<220 V
Protection ratingIP20
Remote signallingyes
Response time<25 ns
Signalling on deviceVisual
SPD to EN 61643-11Type 3
SPD to IEC 61643-1Class III
Test class, type 3yes

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.