OBO BETTERMANN SD15-V24 15 SD15-V24 15 5080150 OBO BETTERMANN Data line protection device for V24 interface D-SUB 15, 12V, View larger
Images are for illustrative purposes only. Please refer to data sheet for details

SD15-V24 15 5080150 OBO BETTERMANN Data line protection device for V24 interface D-SUB 15, 12V,

SD15-V24 15

5080150

OBO BETTERMANN

1 Pcs.

Data line protection device for V24 interface D-SUB 15, 12V, Fine protection for 15-pole RS232 interface. Data cable protection device for serial interfaces• Various connection technologies available• Low voltage protection levelApplication: PLC, alarm systems, controllers

Automation > Surge protection device for data networks/MCR-technology
Surge , arrestor, type 3

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Obo Bettermann SD15-V24 15 data line protection device for V24 interface D-SUB 15, 12V, safeguards serial communication ports against destructive voltage transients induced on cabling networks. Data line protectors are commonly installed in industrial automation architectures to ensure uninterrupted serial data transmission between PLCs and peripherals. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Arrestor monitoring: no
  • CO2 Footprint (GWP) Cradle-to-Gate: 0,0042 kg CO2e / 1 Piece
  • Dimension: 12V
  • Explosion-tested version: no
  • Height: 41,5 mm
  • Impulse durability wire-earth: 0,34 kA (8/20µs)
  • Impulse durability wire-wire: 0,34 kA (8/20µs)
  • Kategorie: Type 3 / C1
  • Length: 60 mm
  • Lightning protection zone LPZ: 2→3
  • Maximum continuous voltage AC: 12 V
  • Maximum continuous voltage DC: 18 V
  • Nominal voltage: 12 V
  • Number of poles: 15
  • Permitted temperature range, max.: 80 °C
  • Permitted temperature range, min.: -40 °C

More info

▲
Arrestor monitoringno
CO2 Footprint (GWP) Cradle-to-Gate0,0042 kg CO2e / 1 Piece
Dimension12V
Explosion-tested versionno
Height41,5 mm
Impulse durability wire-earth0,34 kA (8/20µs)
Impulse durability wire-wire0,34 kA (8/20µs)
KategorieType 3 / C1
Length60 mm
Lightning protection zone LPZ2→3
Maximum continuous voltage AC12 V
Maximum continuous voltage DC18 V
Nominal voltage12 V
Number of poles15
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemD-Sub 15-pin
Protection level wire-earth<50 V
Protection level wire-wire<50 V
Protection level, wire-earth at 1 kV/µs (C3)<25
Protection level, wire-wire at 1 kV/µs (C3)<25 V
Protection ratingIP40
Response time<10 ns
ScreeningDirect
Shielding connection availableyes
SPD to IEC 61643-21Class III / C1
Telecommunications contactno
Testing standardIEC 61643-21
Version forSUB-D-15; V24 RS232
Width16 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.