MDP-4 D-48-T 5098450 OBO BETTERMANN Lightning barrier 4-pole with test function, 48V,
MDP-4 D-48-T
5098450
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Surge , arrestor, type 3
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Obo Bettermann MDP-4 D-48-T lightning barrier 4-pole with test function, 48V operates as a specialized multi-pole surge suppression device engineered to defend communication lines and control loops against lightning-induced surges. These barriers are typically installed inside electrical distribution and control panels to safeguard sensitive processing units from potential overvoltage damage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: UL
- Arrestor monitoring: no
- Capacity (wire-wire): < 40 pF
- CO2 Footprint (GWP) Cradle-to-Gate: 0,3025 kg CO2e / 1 Piece
- Connection cross-section, flexible, max.: 2,5 mm²
- Connection cross-section, flexible, min.: 0,14 mm²
- Connection cross-section, multi-wire, max.: 1,5 mm²
- Connection cross-section, multi-wire, min.: 0,14 mm²
- Connection cross-section, rigid, max.: 2,5 mm²
- Connection cross-section, rigid, min.: 0,14 mm²
- Cut-off frequency: 100 MHz
- Dimension: 48V
- Earthing via:: DIN rail
- Explosion-tested version: no
- Impulse durability wire-earth: C2: 5 kV / 2,5 kA (8/20µs)
- Impulse durability wire-wire: C1: 0,5 kV / 0,25 kA (8/20µs)
More info
▲| Approvals | UL |
|---|---|
| Arrestor monitoring | no |
| Capacity (wire-wire) | < 40 pF |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,3025 kg CO2e / 1 Piece |
| Connection cross-section, flexible, max. | 2,5 mm² |
| Connection cross-section, flexible, min. | 0,14 mm² |
| Connection cross-section, multi-wire, max. | 1,5 mm² |
| Connection cross-section, multi-wire, min. | 0,14 mm² |
| Connection cross-section, rigid, max. | 2,5 mm² |
| Connection cross-section, rigid, min. | 0,14 mm² |
| Cut-off frequency | 100 MHz |
| Dimension | 48V |
| Earthing via: | DIN rail |
| Explosion-tested version | no |
| Impulse durability wire-earth | C2: 5 kV / 2,5 kA (8/20µs) |
| Impulse durability wire-wire | C1: 0,5 kV / 0,25 kA (8/20µs) |
| Insertion loss | ≤3 dB |
| Insulation resistance | >100 MΩ |
| Kategorie | Type 1+2+3 / D1+C2+C1 |
| Lightning protection zone LPZ | 0→3 |
| Maximum continuous voltage AC | 41 V |
| Maximum continuous voltage DC | 58 V |
|---|---|
| Nominal load current AC | 0,4 A |
| Nominal load current DC | 0,58 A |
| Nominal voltage | 48 V |
| Number of poles | 4 |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Plug-in system | Terminal |
| Protection level @ C1 | <110 V |
| Protection level wire-earth | <800 V |
| Protection level wire-wire | <95 V |
| Protection rating | IP20 |
| Screening | Direct |
| Series resistance per wire | 2,35 Ω ± 5 % |
| Shielding connection available | yes |
| Signalling on device | Readable |
| SPD to IEC 61643-21 | Class I+II+III / D1+C2+C1 |
| Telecommunications contact | no |
| Testing standard | IEC 61643-21 |
| Total discharge current (10/350) | D1: 2 kA |
| Total discharge current (8/20) | 10 kA |