MDP-4 D-24-T 5098431 OBO BETTERMANN Lightning barrier 4-pole with test function, 24V,
MDP-4 D-24-T
5098431
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Surge , arrestor, type 3
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Safeguard industrial measurement and control lines from damaging electrical transients with the MDP-4 D-24-T 5098431 OBO BETTERMANN Lightning barrier 4-pole with test function, 24V,. Multi-pole protective devices are widely integrated into automation architectures to defend sensitive data interfaces and low-voltage control loops against indirect lightning strikes and switching surges. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: UL
- Arrestor monitoring: no
- Capacity (wire-earth): <40 pF
- Capacity (wire-wire): <40 pF
- CO2 Footprint (GWP) Cradle-to-Gate: 0,2956 kg CO2e / 1 Piece
- Connection cross-section, flexible, max.: 2,5 mm²
- Connection cross-section, flexible, min.: 0,14 mm²
- Connection cross-section, multi-wire, max.: 1,5 mm²
- Connection cross-section, multi-wire, min.: 0,14 mm²
- Connection cross-section, rigid, max.: 2,5 mm²
- Connection cross-section, rigid, min.: 0,14 mm²
- Cut-off frequency: 100 MHz
- Dimension: 24V
- Earthing via:: DIN rail
- Explosion-tested version: no
- Impulse durability wire-earth: C2: 5 kV / 2,5 kA (8/20µs)
More info
▲| Approvals | UL |
|---|---|
| Arrestor monitoring | no |
| Capacity (wire-earth) | <40 pF |
| Capacity (wire-wire) | <40 pF |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,2956 kg CO2e / 1 Piece |
| Connection cross-section, flexible, max. | 2,5 mm² |
| Connection cross-section, flexible, min. | 0,14 mm² |
| Connection cross-section, multi-wire, max. | 1,5 mm² |
| Connection cross-section, multi-wire, min. | 0,14 mm² |
| Connection cross-section, rigid, max. | 2,5 mm² |
| Connection cross-section, rigid, min. | 0,14 mm² |
| Cut-off frequency | 100 MHz |
| Dimension | 24V |
| Earthing via: | DIN rail |
| Explosion-tested version | no |
| Impulse durability wire-earth | C2: 5 kV / 2,5 kA (8/20µs) |
| Impulse durability wire-wire | C1: 0,5 kV / 0,25 kA (8/20µs) |
| Insertion loss | ≤3 dB |
| Insulation resistance | >100 MΩ |
| Kategorie | Type 1+2+3 / D1+C2+C1 |
| Lightning protection zone LPZ | 0→3 |
| Maximum continuous voltage AC | 20 V |
| Maximum continuous voltage DC | 28 V |
|---|---|
| Nominal load current AC | 0,4 A |
| Nominal load current DC | 0,58 A |
| Nominal voltage | 24 V |
| Number of poles | 4 |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Plug-in system | Terminal |
| Protection level @ C1 | <65 V |
| Protection level wire-earth | <800 V |
| Protection level wire-wire | <55 V |
| Protection rating | IP20 |
| Screening | Direct |
| Series resistance per wire | 2,35 Ω ± 5 % |
| Shielding connection available | yes |
| Signalling on device | Readable |
| SPD to IEC 61643-21 | Class I+II+III / D1+C2+C1 |
| Telecommunications contact | no |
| Testing standard | IEC 61643-21 |
| Total discharge current (10/350) | D1: 2 kA |
| Total discharge current (8/20) | 10 kA |