OBO BETTERMANN FRD 5 FRD 5 5098492 OBO BETTERMANN Lightning barrier with decoupling resistance, 5V AC, View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FRD 5 5098492 OBO BETTERMANN Lightning barrier with decoupling resistance, 5V AC,

FRD 5

5098492

OBO BETTERMANN

1 Pcs.

Lightning barrier with decoupling resistance, 5V AC, Medium and fine protection FRD for two-core systems 5 V. Surge protection for use in measurement and control technology • Medium and fine protection • Standard design for double core systems • Two-stage protection circuit • With installation-friendly, screwless connection terminals • In space-saving 17.5 mm grid • With ohmic decoupling in the longitudinal branchApplication: Universal use on any 35 mm DIN profile rail in every commercially available distributor housing.

Automation > Combined arrester for data networks/MCR-technology
Surge , arrestor, type 3

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ApprovalsUL
Arrestor monitoringno
Capacity (wire-earth)<1 nF
Capacity (wire-wire)<10 nF
CO2 Footprint (GWP) Cradle-to-Gate0,2968 kg CO2e / 1 Piece
Connection cross-section, flexible, max.2,5 mm²
Connection cross-section, flexible, min.0,14 mm²
Connection cross-section, multi-wire, max.2,5 mm²
Connection cross-section, multi-wire, min.0,14 mm²
Connection cross-section, rigid, max.2,5 mm²
Connection cross-section, rigid, min.0,14 mm²
Cut-off frequency0,63 MHz
Dimension5V AC
Division unit TE (17.5 mm)1
Earthing via:Terminal
Explosion-tested versionno
Impulse durability wire-earthC2: 10 kV / 5 kA (8/20µs)
Impulse durability wire-wireC1: 1 kV / 0,5 kA (8/20µs)
Insertion loss3 dB @ 630 kHz dB
Insulation resistance>1 MΩ
KategorieType 1+2+3 / D1+C2+C1
Lightning impulse current1,5 kA
Lightning protection zone LPZ0→3
Maximum continuous voltage AC5 V
Maximum continuous voltage DC8 V
Nominal discharge current (8/20 µs)5 kA
Nominal load current AC0,14 A
Nominal load current DC0,2 A
Nominal voltage5 V
Number of poles2
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemTerminal
Protection level wire-earth<600 V
Protection level wire-wire<15 V
Protection ratingIP20
Series resistance per wire15 Ω ± 10 %
Shielding connection availableno
SPD to IEC 61643-21Class I+II+III / D1+C2+C1
Telecommunications contactno
Testing standardIEC 61643-21
Total discharge current (10/350)D1: 3 kA
Total discharge current (8/20)10 kA

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.