FLD 5 5098600 OBO BETTERMANN Lightning barrier with decoupling inductivity, 5V AC,
FLD 5
5098600
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Surge , arrestor, type 3
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Obo Bettermann FLD 5 lightning barrier with decoupling inductivity, 5V AC functions as an integrated protective component designed to safeguard sensitive electronic measurement and control loops against transient overvoltages and high-energy surges caused by atmospheric discharges or switching operations. Devices of this type are typically installed in industrial control cabinets to protect downstream equipment by safely diverting surge currents to the grounding system while maintaining normal signal transmission. Final pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: UL
- Capacity (wire-earth): <1 nF
- Capacity (wire-wire): <10 nF
- CO2 Footprint (GWP) Cradle-to-Gate: 0,2664 kg CO2e / 1 Piece
- Connection cross-section, flexible, max.: 2,5 mm²
- Connection cross-section, flexible, min.: 0,14 mm²
- Connection cross-section, multi-wire, max.: 2,5 mm²
- Connection cross-section, multi-wire, min.: 0,14 mm²
- Connection cross-section, rigid, max.: 2,5 mm²
- Connection cross-section, rigid, min.: 0,14 mm²
- Cut-off frequency: 0,18 MHz
- Dimension: 5V AC
- Division unit TE (17.5 mm): 1
- Earthing via:: Terminal
- Explosion-tested version: no
- Impulse durability wire-earth: C2: 10 kV / 5 kA (8/20µs)
More info
▲| Approvals | UL |
|---|---|
| Capacity (wire-earth) | <1 nF |
| Capacity (wire-wire) | <10 nF |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,2664 kg CO2e / 1 Piece |
| Connection cross-section, flexible, max. | 2,5 mm² |
| Connection cross-section, flexible, min. | 0,14 mm² |
| Connection cross-section, multi-wire, max. | 2,5 mm² |
| Connection cross-section, multi-wire, min. | 0,14 mm² |
| Connection cross-section, rigid, max. | 2,5 mm² |
| Connection cross-section, rigid, min. | 0,14 mm² |
| Cut-off frequency | 0,18 MHz |
| Dimension | 5V AC |
| Division unit TE (17.5 mm) | 1 |
| Earthing via: | Terminal |
| Explosion-tested version | no |
| Impulse durability wire-earth | C2: 10 kV / 5 kA (8/20µs) |
| Impulse durability wire-wire | C1: 1 kV / 0,5 kA (8/20µs) |
| Insertion loss | 3 dB @ 180 kHz dB |
| Insulation resistance | >1 MΩ |
| Kategorie | Type 1+2+3 / D1+C2+C1 |
| Lightning impulse current | 1,5 kA |
| Lightning protection zone LPZ | 0→3 |
|---|---|
| Maximum continuous voltage AC | 5 V |
| Maximum continuous voltage DC | 8 V |
| Nominal discharge current (8/20 µs) | 5 kA |
| Nominal load current AC | 0,7 A |
| Nominal load current DC | 1 A |
| Number of poles | 2 |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Plug-in system | Terminal |
| Protection level wire-earth | <600 V |
| Protection level wire-wire | <15 V |
| Protection rating | IP20 |
| Series inductivity per wire | 120 µH ± 20 % |
| Shielding connection available | no |
| SPD to IEC 61643-21 | Class I+II+III / D1+C2+C1 |
| Telecommunications contact | no |
| Testing standard | IEC 61643-21 |
| Total discharge current (10/350) | D1: 3 kA |
| Total discharge current (8/20) | 10 kA |