FLD 12 5098603 OBO BETTERMANN Lightning barrier with decoupling inductivity, 12V AC,
FLD 12
5098603
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Surge , arrestor, type 3
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Obo Bettermann lightning barrier (part number FLD 12) is designed to attenuate high-energy surge currents and protect low-voltage electrical systems from switching transients and atmospheric discharges. These protective modules are commonly deployed in industrial distribution panels to ensure system reliability. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: UL
- Capacity (wire-earth): <1 nF
- Capacity (wire-wire): <10 nF
- CO2 Footprint (GWP) Cradle-to-Gate: 0,2713 kg CO2e / 1 Piece
- Connection cross-section, flexible, max.: 2,5 mm²
- Connection cross-section, flexible, min.: 0,14 mm²
- Connection cross-section, multi-wire, max.: 2,5 mm²
- Connection cross-section, multi-wire, min.: 0,14 mm²
- Connection cross-section, rigid, max.: 2,5 mm²
- Connection cross-section, rigid, min.: 0,14 mm²
- Cut-off frequency: 0,18 MHz
- Dimension: 12V AC
- Division unit TE (17.5 mm): 1
- Earthing via:: Terminal
- Explosion-tested version: no
- Impulse durability wire-earth: C2: 10 kV / 5 kA (8/20µs)
More info
▲| Approvals | UL |
|---|---|
| Capacity (wire-earth) | <1 nF |
| Capacity (wire-wire) | <10 nF |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,2713 kg CO2e / 1 Piece |
| Connection cross-section, flexible, max. | 2,5 mm² |
| Connection cross-section, flexible, min. | 0,14 mm² |
| Connection cross-section, multi-wire, max. | 2,5 mm² |
| Connection cross-section, multi-wire, min. | 0,14 mm² |
| Connection cross-section, rigid, max. | 2,5 mm² |
| Connection cross-section, rigid, min. | 0,14 mm² |
| Cut-off frequency | 0,18 MHz |
| Dimension | 12V AC |
| Division unit TE (17.5 mm) | 1 |
| Earthing via: | Terminal |
| Explosion-tested version | no |
| Impulse durability wire-earth | C2: 10 kV / 5 kA (8/20µs) |
| Impulse durability wire-wire | C1: 1 kV / 0,5 kA (8/20µs) |
| Insertion loss | 3 dB @ 180 kHz dB |
| Insulation resistance | >1 MΩ |
| Kategorie | Type 1+2+3 / D1+C2+C1 |
| Lightning impulse current | 1,5 kA |
| Lightning protection zone LPZ | 0→3 |
|---|---|
| Maximum continuous voltage AC | 9 V |
| Maximum continuous voltage DC | 13 V |
| Nominal discharge current (8/20 µs) | 5 kA |
| Nominal load current AC | 0,7 A |
| Nominal load current DC | 1 A |
| Number of poles | 2 |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Plug-in system | Terminal |
| Protection level wire-earth | <600 V |
| Protection level wire-wire | <30 V |
| Protection rating | IP20 |
| Series inductivity per wire | 120 µH ± 20 % |
| Shielding connection available | no |
| SPD to IEC 61643-21 | Class I+II+III / D1+C2+C1 |
| Telecommunications contact | no |
| Testing standard | IEC 61643-21 |
| Total discharge current (10/350) | D1: 3 kA |
| Total discharge current (8/20) | 10 kA |