View larger
DS-F M/W 5093275 OBO BETTERMANN Protection device for high-frequency cables, 130V,
DS-F M/W
5093275
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Surge , arrestor, type 3
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protection device for high-frequency cables by Obo Bettermann, specifically part number DS-F M/W, is engineered to safeguard sensitive communication lines against transient overvoltages and high-frequency interference in industrial control networks. Such components are typically installed at signal entry points to divert damaging surges safely to ground while maintaining signal integrity. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Max. continuous voltage AC (EF004198): 130 V
- Max. continuous voltage DC (EF004777): 185 V
- Voltage protection level core/core (EF004233): 800 V
- Voltage protection level core/earth (EF004234): 800 V
- With remote signalling contact (EF000422): No
- Degree of protection (IP) (EF005474): IP40
More info
▲| Arrestor monitoring | no |
|---|---|
| Capacity (wire-earth) | <20 pF |
| Capacity (wire-wire) | <10 pF |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,1274 kg CO2e / 1 Piece |
| Cut-off frequency | 3400 MHz |
| Dimension | 130V |
| Explosion-tested version | no |
| Impulse durability wire-earth | C2: 10 kV / 5 kA (8/20µs) |
| Impulse durability wire-wire | C2: 10 kV / 5 kA (8/20µs) |
| Insertion loss | ≤0,9 dB |
| Insulation resistance | >1 GΩ |
| Kategorie | Type 1+2 / D1+C2 |
| Lightning impulse current | 1 kA |
| Lightning protection zone LPZ | 0→2 |
| Maximum continuous voltage AC | 130 V |
| Maximum continuous voltage DC | 185 V |
| Nominal load current AC | 3,5 A |
| Nominal load current DC | 5 A |
| Number of poles | 1 |
|---|---|
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Plug-in system | F |
| Protection level | <800 V |
| Protection level wire-earth | <800 V |
| Protection level wire-wire | <800 V |
| Protection rating | IP40 |
| Return loss | ≥14 dB |
| Screening | Direct |
| Shielding connection available | yes |
| Signalling on device | None |
| SPD to IEC 61643-21 | Class I+II / D1+C2 |
| Telecommunications contact | no |
| Testing standard | IEC 61643-21 |
| Total discharge current (10/350) | D1: 2 kA |
| Total discharge current (8/20) | 10 kA |
| Wave resistance | 75 Ω |