View larger
V50-B+C 1+NPE+FS 5093661 OBO BETTERMANN CombiController V50 1-pole + NPE w. remote signal, 280V,
V50-B+C 1+NPE+FS
5093661
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for power supply systems
Surge , arrestor, type 1+2 (office housing)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Serving as an integrated protection solution, the V50-B+C 1+NPE+FS 5093661 OBO BETTERMANN CombiController V50 1-pole + NPE w. remote signal, 280V, is designed to shield single-phase electrical systems from severe transient overvoltages. It is typically deployed at main service entrances to divert lightning currents and switching spikes away from sensitive circuits. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Arrester surge current (8/20 µs) [total]: 50 kA
- Blow-out: no
- CO2 Footprint (GWP) Cradle-to-Gate: 1,1123 kg CO2e / 1 Piece
- Conductor cross-section, rigid (single-wire/multiwire), max.: 35 mm²
- Conductor cross-section, rigid (single-wire/multiwire), min.: 2,5 mm²
- DC network form: no
- Dimension: 280V
- Installation type: DIN rail 35 mm
- Integrated back-up fuse: no
- IT network form: no
- Lightning protection zone LPZ: 0→2
- Lightning surge current (10/350 μs): 12,5 kA
- Lightning surge current (10/350): 25 kA
- Max. mains-side overcurrent protection: 125
- Maximum back-up fuse: 125 A
- Maximum continuous voltage (N-PE): 255 V
More info
▲| Arrester surge current (8/20 µs) [total] | 50 kA |
|---|---|
| Blow-out | no |
| CO2 Footprint (GWP) Cradle-to-Gate | 1,1123 kg CO2e / 1 Piece |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 35 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 2,5 mm² |
| DC network form | no |
| Dimension | 280V |
| Installation type | DIN rail 35 mm |
| Integrated back-up fuse | no |
| IT network form | no |
| Lightning protection zone LPZ | 0→2 |
| Lightning surge current (10/350 μs) | 12,5 kA |
| Lightning surge current (10/350) | 25 kA |
| Max. mains-side overcurrent protection | 125 |
| Maximum back-up fuse | 125 A |
| Maximum continuous voltage (N-PE) | 255 V |
| Maximum continuous voltage AC | 280 V |
| Maximum discharge current (8/20 μs) | 50 kA |
| Network form | Other |
| Nominal discharge current (8/20 µs) | 30 kA |
| Nominal discharge current (8/20 µs) [L-N] | 30 kA |
| Nominal discharge current (8/20 µs) [N-PE] | 50 kA |
| Nominal voltage AC (50/60 Hz) | 230 V |
|---|---|
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
| Other network form | no |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Pole number | 1 |
| Pole version | 1+N/PE |
| Protection level [L-N] | ≤1,3 |
| Protection rating | IP20 |
| Remote signalling | yes |
| Response time | <25 ns |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 1+2 |
| SPD to IEC 61643-1 | Class I+II |
| TN network form | yes |
| TN-C network form | no |
| TN-C-S network form | yes |
| TN-S network form | yes |
| TT network form | yes |
| Version for | 1+NPE + FS |