View larger
V25-B+C 1-280 5094418 OBO BETTERMANN CombiController V25 single pole version, 280V,
V25-B+C 1-280
5094418
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for power supply systems
Surge , arrestor, type 1+2 (office housing)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The V25-B+C 1-280 5094418 OBO BETTERMANN CombiController V25 single pole version, 280V, is a versatile surge protective device designed to limit transient overvoltages in industrial and commercial power distribution architectures. It effectively diverts sudden electrical surges to ground, preserving the functional integrity of downstream assets. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Arrester surge current (8/20 µs) [total]: 30 kA
- Blow-out: no
- CO2 Footprint (GWP) Cradle-to-Gate: 0,4896 kg CO2e / 1 Piece
- Conductor cross-section, rigid (single-wire/multiwire), max.: 35 mm²
- Conductor cross-section, rigid (single-wire/multiwire), min.: 2,5 mm²
- Dimension: 280V
- Lightning protection zone LPZ: 0→2
- Lightning surge current (10/350 μs): 7 kA
- Lightning surge current (10/350): 7 kA
- Max. mains-side overcurrent protection: 160
- Maximum back-up fuse: 160 A
- Maximum continuous voltage AC: 280 V
- Maximum continuous voltage DC: 200 V
- Maximum discharge current (8/20 μs): 50 kA
- Network form: TN
- Nominal discharge current (8/20 µs): 30 kA
More info
▲| Arrester surge current (8/20 µs) [total] | 30 kA |
|---|---|
| Blow-out | no |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,4896 kg CO2e / 1 Piece |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 35 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 2,5 mm² |
| Dimension | 280V |
| Lightning protection zone LPZ | 0→2 |
| Lightning surge current (10/350 μs) | 7 kA |
| Lightning surge current (10/350) | 7 kA |
| Max. mains-side overcurrent protection | 160 |
| Maximum back-up fuse | 160 A |
| Maximum continuous voltage AC | 280 V |
| Maximum continuous voltage DC | 200 V |
| Maximum discharge current (8/20 μs) | 50 kA |
| Network form | TN |
| Nominal discharge current (8/20 µs) | 30 kA |
| Nominal discharge current (8/20 µs) [L-N] | 30 kA |
| Nominal discharge current (8/20 µs) [N-PE] | 30 kA |
| Nominal voltage AC (50/60 Hz) | 230 V |
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
|---|---|
| Other network form | yes |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Pole number | 1 |
| Pole version | 1 |
| Protection rating | IP20 |
| Remote signalling | no |
| Response time | <25 ns |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 1+2 |
| SPD to IEC 61643-1 | Class I+II |
| Test class, type 2 | yes |
| TN network form | yes |
| TN-C network form | yes |
| TN-C-S network form | yes |
| TN-S network form | yes |
| TT network form | yes |
| Version for | 1-pole |