View larger
5095312 OBO BETTERMANN DOWNLOADER T. 2 V20-2+FS-550
V20-2+FS-550
5095312
OBO BETTERMANN
1 Pcs.
Automation > Surge protection device for power supply systems
TBS Transient and lightning protection systems - OBO BETTERMANN
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Obo Bettermann engineered the 5095312 OBO BETTERMANN DOWNLOADER T. 2 V20-2+FS-550 to provide robust defense against electrical overvoltages in demanding industrial environments. These protective devices are installed upstream of sensitive machinery to absorb high-energy transient spikes and ensure continuous operational safety. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: UL
- Arrester surge current (8/20 µs) [total]: 80 kA
- Blow-out: no
- CO2 Footprint (GWP) Cradle-to-Gate: 1,0904 kg CO2e / 1 Piece
- Conductor cross-section, flexible (fine-wire), max.: 2 AWG
- Conductor cross-section, flexible (fine-wire), max.: 35 mm²
- Conductor cross-section, flexible (fine-wire), min.: 16 AWG
- Conductor cross-section, flexible (fine-wire), min.: 1,5 mm²
- Conductor cross-section, rigid (single-wire/multiwire), max.: 35 mm²
- Conductor cross-section, rigid (single-wire/multiwire), max.: 2 AWG
- Conductor cross-section, rigid (single-wire/multiwire), min.: 1,5 mm²
- Conductor cross-section, rigid (single-wire/multiwire), min.: 16 AWG
- Connection cross-section, FM terminals, max.: 1,5 mm²
- Connection cross-section, FM terminals, max.: 16 AWG
- Connection cross-section, FM terminals, min.: 21 AWG
- Connection cross-section, FM terminals, min.: 0,5 mm²
More info
▲| Approvals | UL |
|---|---|
| Arrester surge current (8/20 µs) [total] | 80 kA |
| Blow-out | no |
| CO2 Footprint (GWP) Cradle-to-Gate | 1,0904 kg CO2e / 1 Piece |
| Conductor cross-section, flexible (fine-wire), max. | 2 AWG |
| Conductor cross-section, flexible (fine-wire), max. | 35 mm² |
| Conductor cross-section, flexible (fine-wire), min. | 16 AWG |
| Conductor cross-section, flexible (fine-wire), min. | 1,5 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 35 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 2 AWG |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 1,5 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 16 AWG |
| Connection cross-section, FM terminals, max. | 1,5 mm² |
| Connection cross-section, FM terminals, max. | 16 AWG |
| Connection cross-section, FM terminals, min. | 21 AWG |
| Connection cross-section, FM terminals, min. | 0,5 mm² |
| Dimension | 550V |
| FM contacts | Changeover |
| Housing material surge protection components | PA UL 94 V-0 |
| Installation type | DIN rail 35 mm |
| Integrated back-up fuse | no |
| Max. mains-side overcurrent protection | 160 A gL/gG |
| Maximum back-up fuse | 160 A |
| Maximum continuous voltage (L-N) | 550 V |
| Maximum continuous voltage AC | 550 V |
| Maximum discharge current (8/20 μs) | 40 kA |
| Maximum discharge current (8/20 μs) [L-N] | 40 kA |
| Minimum distance | 1,5 mm |
| Network form | Other |
| Nominal discharge current (8/20 µs) | 15 kA |
|---|---|
| Nominal discharge current (8/20 µs) [L-N] | 20 kA |
| Nominal voltage AC (50/60 Hz) | 480 V |
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Pole number | 2 |
| Pole version | 2 |
| Protection level [L-N] | ≤2,4 |
| Protection rating | IP20 |
| Remote signalling | yes |
| Residual voltage [L-N] @ 1 kA | 1,7 kV |
| Residual voltage [L-N] @ 5 kA | 2,1 kV |
| Response time | <25 ns |
| Short-circuit resistance for max. mains-side overcurrent protection | 50 kA eff |
| Short-circuit resistant | yes |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 2 |
| SPD to IEC 61643-1 | Class II |
| SPD to UL 1449 | Type 4 |
| Switching power AC | 230 V; 0,5 A |
| Switching power DC | 230 V; 0,1 A / 75 V; 0,5 A |
| Test class, type 2 | yes |
| TN network form | yes |
| TN-C network form | yes |
| Torque | 4 Nm |
| TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. | 915 V |
| TOV voltage [L-N] ‒ withstand mode ‒ 5 s | 700 V |