View larger
5095302 OBO BETTERMANN DOWNLOADER T. 2 V20-2+FS-385
V20-2+FS-385
5095302
OBO BETTERMANN
1 Pcs.
Automation > Surge protection device for power supply systems
TBS Transient and lightning protection systems - OBO BETTERMANN
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Obo Bettermann supplies the 5095302 OBO BETTERMANN DOWNLOADER T. 2 V20-2+FS-385 to manage transient overvoltages within electrical installations. Class II surge arresters are integrated into low-voltage distribution systems to limit surge amplitudes and protect downstream electrical loads from destruction. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: VDE, KEMA, UL, ÖVE
- Arrester surge current (8/20 µs) [total]: 80 kA
- Blow-out: no
- CO2 Footprint (GWP) Cradle-to-Gate: 1,1926 kg CO2e / 1 Piece
- Conductor cross-section, flexible (fine-wire), max.: 35 mm²
- Conductor cross-section, flexible (fine-wire), max.: 2 AWG
- Conductor cross-section, flexible (fine-wire), min.: 1,5 mm²
- Conductor cross-section, flexible (fine-wire), min.: 16 AWG
- Conductor cross-section, rigid (single-wire/multiwire), max.: 2 AWG
- Conductor cross-section, rigid (single-wire/multiwire), max.: 35 mm²
- Conductor cross-section, rigid (single-wire/multiwire), min.: 16 AWG
- Conductor cross-section, rigid (single-wire/multiwire), min.: 1,5 mm²
- Connection cross-section, FM terminals, max.: 1,5 mm²
- Connection cross-section, FM terminals, max.: 16 AWG
- Connection cross-section, FM terminals, min.: 0,5 mm²
- Connection cross-section, FM terminals, min.: 21 AWG
More info
▲| Approvals | VDE, KEMA, UL, ÖVE |
|---|---|
| Arrester surge current (8/20 µs) [total] | 80 kA |
| Blow-out | no |
| CO2 Footprint (GWP) Cradle-to-Gate | 1,1926 kg CO2e / 1 Piece |
| Conductor cross-section, flexible (fine-wire), max. | 35 mm² |
| Conductor cross-section, flexible (fine-wire), max. | 2 AWG |
| Conductor cross-section, flexible (fine-wire), min. | 1,5 mm² |
| Conductor cross-section, flexible (fine-wire), min. | 16 AWG |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 2 AWG |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 35 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 16 AWG |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 1,5 mm² |
| Connection cross-section, FM terminals, max. | 1,5 mm² |
| Connection cross-section, FM terminals, max. | 16 AWG |
| Connection cross-section, FM terminals, min. | 0,5 mm² |
| Connection cross-section, FM terminals, min. | 21 AWG |
| Dimension | 385V |
| FM contacts | Changeover |
| Housing material surge protection components | PA UL 94 V-0 |
| Installation type | DIN rail 35 mm |
| Integrated back-up fuse | no |
| Max. mains-side overcurrent protection | 160 A gL/gG |
| Maximum back-up fuse | 160 A |
| Maximum continuous voltage (L-N) | 385 V |
| Maximum continuous voltage AC | 385 V |
| Maximum discharge current (8/20 μs) | 40 kA |
| Maximum discharge current (8/20 μs) [L-N] | 40 kA |
| Minimum distance | 1,5 mm |
| Network form | Other |
| Nominal discharge current (8/20 µs) | 20 kA |
|---|---|
| Nominal discharge current (8/20 µs) [L-N] | 20 kA |
| Nominal voltage AC (50/60 Hz) | 350 V |
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Pole number | 2 |
| Pole version | 2 |
| Protection level [L-N] | ≤1,7 |
| Protection rating | IP20 |
| Remote signalling | yes |
| Residual voltage [L-N] @ 1 kA | 1,2 kV |
| Residual voltage [L-N] @ 5 kA | 1,4 kV |
| Response time | <25 ns |
| Short-circuit resistance for max. mains-side overcurrent protection | 50 kA eff |
| Short-circuit resistant | yes |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 2 |
| SPD to IEC 61643-1 | Class II |
| SPD to UL 1449 | Type 4 |
| Switching power AC | 230 V; 0,5 A |
| Switching power DC | 230 V; 0,1 A / 75 V; 0,5 A |
| Test class, type 2 | yes |
| TN network form | yes |
| TN-C network form | yes |
| Torque | 4 Nm |
| TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. | 670 V |
| TOV voltage [L-N] ‒ withstand mode ‒ 5 s | 510 V |