View larger
5095284 OBO BETTERMANN DOWNLOADER T. 2 V20-4+FS-280
V20-4+FS-280
5095284
OBO BETTERMANN
1 Pcs.
Automation > Surge protection device for power supply systems
TBS Transient and lightning protection systems - OBO BETTERMANN
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The 5095284 OBO BETTERMANN DOWNLOADER T. 2 V20-4+FS-280 is a robust multi-pole surge protection device built for commercial and industrial electrical grids. These units are typically installed upstream in power distribution boards to limit voltage spikes and protect sensitive internal circuits from lightning or switching transients. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: VDE, KEMA, UL, ÖVE
- Arrester surge current (8/20 µs) [total]: 160 kA
- Blow-out: no
- CO2 Footprint (GWP) Cradle-to-Gate: 1,9185 kg CO2e / 1 Piece
- Conductor cross-section, flexible (fine-wire), max.: 2 AWG
- Conductor cross-section, flexible (fine-wire), max.: 35 mm²
- Conductor cross-section, flexible (fine-wire), min.: 16 AWG
- Conductor cross-section, flexible (fine-wire), min.: 1,5 mm²
- Conductor cross-section, rigid (single-wire/multiwire), max.: 35 mm²
- Conductor cross-section, rigid (single-wire/multiwire), max.: 2 AWG
- Conductor cross-section, rigid (single-wire/multiwire), min.: 1,5 mm²
- Conductor cross-section, rigid (single-wire/multiwire), min.: 16 AWG
- Connection cross-section, FM terminals, max.: 1,5 mm²
- Connection cross-section, FM terminals, max.: 16 AWG
- Connection cross-section, FM terminals, min.: 21 AWG
- Connection cross-section, FM terminals, min.: 0,5 mm²
More info
▲| Approvals | VDE, KEMA, UL, ÖVE |
|---|---|
| Arrester surge current (8/20 µs) [total] | 160 kA |
| Blow-out | no |
| CO2 Footprint (GWP) Cradle-to-Gate | 1,9185 kg CO2e / 1 Piece |
| Conductor cross-section, flexible (fine-wire), max. | 2 AWG |
| Conductor cross-section, flexible (fine-wire), max. | 35 mm² |
| Conductor cross-section, flexible (fine-wire), min. | 16 AWG |
| Conductor cross-section, flexible (fine-wire), min. | 1,5 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 35 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 2 AWG |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 1,5 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 16 AWG |
| Connection cross-section, FM terminals, max. | 1,5 mm² |
| Connection cross-section, FM terminals, max. | 16 AWG |
| Connection cross-section, FM terminals, min. | 21 AWG |
| Connection cross-section, FM terminals, min. | 0,5 mm² |
| Dimension | 280V |
| FM contacts | Changeover |
| Housing material surge protection components | PA UL 94 V-0 |
| Installation type | DIN rail 35 mm |
| Integrated back-up fuse | no |
| Max. mains-side overcurrent protection | 160 A gL/gG |
| Maximum back-up fuse | 160 A |
| Maximum continuous voltage (L-N) | 280 V |
| Maximum continuous voltage (N-PE) | 255 V |
| Maximum continuous voltage AC | 280 V |
| Maximum discharge current (8/20 μs) | 40 kA |
| Maximum discharge current (8/20 μs) [L-N] | 40 kA |
| Minimum distance | 1,5 mm |
| Network form | Other |
| Nominal discharge current (8/20 µs) | 20 kA |
|---|---|
| Nominal discharge current (8/20 µs) [L-N] | 20 kA |
| Nominal voltage AC (50/60 Hz) | 230 V |
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Pole number | 4 |
| Pole version | 4 |
| Protection level [L-N] | ≤1,3 |
| Protection rating | IP20 |
| Remote signalling | yes |
| Residual voltage [L-N] @ 1 kA | 0,8 kV |
| Residual voltage [L-N] @ 5 kA | 1 kV |
| Response time | <25 ns |
| Short-circuit resistance for max. mains-side overcurrent protection | 50 kA eff |
| Short-circuit resistant | yes |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 2 |
| SPD to IEC 61643-1 | Class II |
| SPD to UL 1449 | Type 4 |
| Switching power AC | 230 V; 0,5 A |
| Switching power DC | 230 V; 0,1 A / 75 V; 0,5 A |
| Test class, type 2 | yes |
| TN network form | yes |
| TN-C-S network form | yes |
| TN-S network form | yes |
| Torque | 4 Nm |
| TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. | 440 V |
| TOV voltage [L-N] ‒ withstand mode ‒ 5 s | 335 V |