OBO BETTERMANN V20-3+NPE-150 5095233 OBO BETTERMANN DOWNLOADER T. 2 V20-3+NPE-150 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

5095233 OBO BETTERMANN DOWNLOADER T. 2 V20-3+NPE-150

V20-3+NPE-150

5095233

OBO BETTERMANN

1 Pcs.

DOWNLOADER T. 2 V20-3+NPE-150 Surge arrester V20, 3-pole + NPE, 150 V. Surge arrester, type 2• For surge voltage protection equipotential bonding to VDE 0100-443 (IEC 60364-4-44)• Discharge capacity to 40 kA (8/20) per pole through high-performance varistors • Modular connectable arrester with cut-off unit and visual status display • Locking mechanism with vibration protection and voltage keying • Plastic to UL 94 V-0• The remote signalling variants (FS) have a potential-free changeover contact for remote signallingApplication: Equipotential bonding in main and sub-distributions.

Automation > Surge protection device for power supply systems
TBS Transient and lightning protection systems - OBO BETTERMANN

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Designed for multi-phase electrical networks, the 5095233 OBO BETTERMANN DOWNLOADER T. 2 V20-3+NPE-150 operates as a comprehensive type 2 surge arrester. These assemblies provide coordinated multi-path protection to safeguard phase lines and neutral-to-earth configurations from unexpected voltage surges in industrial environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Approvals: VDE, KEMA, UL, ÖVE
  • Arrester surge current (8/20 µs) [total]: 60 kA
  • Blow-out: no
  • CO2 Footprint (GWP) Cradle-to-Gate: 1,9534 kg CO2e / 1 Piece
  • Combined voltage protection level [L-PE]: 1,2 kV
  • Conductor cross-section, flexible (fine-wire), max.: 35 mm²
  • Conductor cross-section, flexible (fine-wire), max.: 2 AWG
  • Conductor cross-section, flexible (fine-wire), min.: 16 AWG
  • Conductor cross-section, flexible (fine-wire), min.: 1,5 mm²
  • Conductor cross-section, rigid (single-wire/multiwire), max.: 2 AWG
  • Conductor cross-section, rigid (single-wire/multiwire), max.: 35 mm²
  • Conductor cross-section, rigid (single-wire/multiwire), min.: 1,5 mm²
  • Conductor cross-section, rigid (single-wire/multiwire), min.: 16 AWG
  • Dimension: 150V
  • Follow current quenching capacity (eff) [N-PE]: 0,1 kA
  • Housing material surge protection components: PA UL 94 V-0

More info

▲
ApprovalsVDE, KEMA, UL, ÖVE
Arrester surge current (8/20 µs) [total]60 kA
Blow-outno
CO2 Footprint (GWP) Cradle-to-Gate1,9534 kg CO2e / 1 Piece
Combined voltage protection level [L-PE]1,2 kV
Conductor cross-section, flexible (fine-wire), max.35 mm²
Conductor cross-section, flexible (fine-wire), max.2 AWG
Conductor cross-section, flexible (fine-wire), min.16 AWG
Conductor cross-section, flexible (fine-wire), min.1,5 mm²
Conductor cross-section, rigid (single-wire/multiwire), max.2 AWG
Conductor cross-section, rigid (single-wire/multiwire), max.35 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.1,5 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.16 AWG
Dimension150V
Follow current quenching capacity (eff) [N-PE]0,1 kA
Housing material surge protection componentsPA UL 94 V-0
Installation typeDIN rail 35 mm
Integrated back-up fuseno
Max. mains-side overcurrent protection160 A gL/gG
Maximum back-up fuse160 A
Maximum continuous voltage (L-N)150 V
Maximum continuous voltage (N-PE)255 V
Maximum continuous voltage AC150 V
Maximum discharge current (8/20 μs)40 kA
Maximum discharge current (8/20 μs) [L-N]40 kA
Maximum discharge current (8/20 μs) [N-PE]60 kA
Minimum distance1,5 mm
Network formOther
Nominal discharge current (8/20 µs)20 kA
Nominal discharge current (8/20 µs) [L-N]20 kA
Nominal discharge current (8/20 µs) [N-PE]40 kA
Nominal voltage AC (50/60 Hz)120 V
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Pole number4
Pole version3+N/PE
Protection level [L-N]≤0,8
Protection ratingIP20
Remote signallingno
Residual voltage [L-N] @ 1 kA0,5 kV
Residual voltage [L-N] @ 5 kA0,6 kV
Response time<25 ns
Short-circuit resistance for max. mains-side overcurrent protection50 kA eff
Short-circuit resistantyes
Signalling on deviceVisual
SPD to EN 61643-11Type 2
SPD to IEC 61643-1Class II
SPD to UL 1449Type 4
Test class, type 2yes
TN network formyes
TN-C-S network formyes
TN-S network formyes
Torque4 Nm
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min.230 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s175 V
TOV voltage [N-PE] ‒ withstand mode ‒ 200 ms1200 V
TT network formyes

Product Datasheet