View larger
5093508 OBO BETTERMANN ARRESTER 1+2 V50-0-280
V50-0-280
5093508
OBO BETTERMANN
1 Pcs.
Automation > Combined arrester for power supply systems
TBS Transient and lightning protection systems - OBO BETTERMANN
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Acting as an essential surge protective component, the Obo Bettermann 5093508 OBO BETTERMANN ARRESTER 1+2 V50-0-280 helps shield electrical systems from voltage spikes caused by switching operations or atmospheric phenomena. These devices are typically integrated into power distribution enclosures to limit transient overvoltages and protect sensitive facility machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Approvals: VDE, KEMA, UL, ÖVE
- Blow-out: no
- CO2 Footprint (GWP) Cradle-to-Gate: 0,2165 kg CO2e / 1 Piece
- Conductor cross-section, flexible (fine-wire), max.: 2 AWG
- Conductor cross-section, flexible (fine-wire), max.: 35 mm²
- Conductor cross-section, flexible (fine-wire), min.: 16 AWG
- Conductor cross-section, flexible (fine-wire), min.: 1,5 mm²
- Conductor cross-section, rigid (single-wire/multiwire), max.: 35 mm²
- Conductor cross-section, rigid (single-wire/multiwire), max.: 2 AWG
- Conductor cross-section, rigid (single-wire/multiwire), min.: 16 AWG
- Conductor cross-section, rigid (single-wire/multiwire), min.: 1,5 mm²
- Connection cross-section, FM terminals, max.: 16 AWG
- Connection cross-section, FM terminals, max.: 1,5 mm²
- Connection cross-section, FM terminals, min.: 21 AWG
- Connection cross-section, FM terminals, min.: 0,5 mm²
- Dimension: 280V
More info
▲| Approvals | VDE, KEMA, UL, ÖVE |
|---|---|
| Blow-out | no |
| CO2 Footprint (GWP) Cradle-to-Gate | 0,2165 kg CO2e / 1 Piece |
| Conductor cross-section, flexible (fine-wire), max. | 2 AWG |
| Conductor cross-section, flexible (fine-wire), max. | 35 mm² |
| Conductor cross-section, flexible (fine-wire), min. | 16 AWG |
| Conductor cross-section, flexible (fine-wire), min. | 1,5 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 35 mm² |
| Conductor cross-section, rigid (single-wire/multiwire), max. | 2 AWG |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 16 AWG |
| Conductor cross-section, rigid (single-wire/multiwire), min. | 1,5 mm² |
| Connection cross-section, FM terminals, max. | 16 AWG |
| Connection cross-section, FM terminals, max. | 1,5 mm² |
| Connection cross-section, FM terminals, min. | 21 AWG |
| Connection cross-section, FM terminals, min. | 0,5 mm² |
| Dimension | 280V |
| Housing material surge protection components | PA UL 94 V-0 |
| Installation type | DIN rail 35 mm |
| Integrated back-up fuse | no |
| Lightning surge current (10/350 μs) | 12,5 kA |
| Max. mains-side overcurrent protection | 160 A gL/gG |
| Maximum back-up fuse | 160 A |
| Maximum continuous voltage (L-N) | 280 V |
| Maximum continuous voltage AC | 280 V |
| Maximum discharge current (8/20 μs) | 50 kA |
| Maximum discharge current (8/20 μs) [L-N] | 50 kA |
| Minimum distance | 1,5 mm |
|---|---|
| Network form | All |
| Nominal discharge current (8/20 µs) | 30 kA |
| Nominal discharge current (8/20 µs) [L-N] | 30 kA |
| Nominal voltage AC (50/60 Hz) | 230 V |
| Operating temperature, max. | 80 °C |
| Operating temperature, min. | -40 °C |
| Permitted temperature range, max. | 80 °C |
| Permitted temperature range, min. | -40 °C |
| Pole number | 1 |
| Pole version | 1 |
| Protection level [L-N] | ≤1,3 |
| Protection rating | IP20 |
| Remote signalling | no |
| Residual voltage [L-N] @ 1 kA | 0,7 kV |
| Residual voltage [L-N] @ 12.5 kA | 1 kV |
| Residual voltage [L-N] @ 5 kA | 0,8 kV |
| Response time | <25 ns |
| Short-circuit resistance for max. mains-side overcurrent protection | 50 kA eff |
| Signalling on device | Visual |
| SPD to EN 61643-11 | Type 1+2 |
| SPD to IEC 61643-1 | Class I+II |
| SPD to UL 1449 | Type 4 |
| Torque | 4 Nm |
| TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. | 440 V |
| TOV voltage [L-N] ‒ withstand mode ‒ 5 s | 335 V |