OBO BETTERMANN V50-1+NPE-150 V50-1+NPE-150 5093452 OBO BETTERMANN ARRESTER 1+2 V50-1+NPE-150 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

V50-1+NPE-150 5093452 OBO BETTERMANN ARRESTER 1+2 V50-1+NPE-150

V50-1+NPE-150

5093452

OBO BETTERMANN

1 Pcs.

ARRESTER 1+2 V50-1+NPE-150 Combined discharger V50 V50-1+NPE-150.1 pole with NPE 150V Polyamide, PA,

Automation > Combined arrester for power supply systems
TBS Transient and lightning protection systems - OBO BETTERMANN

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Obo Bettermann V50-1+NPE-150 arrester 1+2 provides dependable transient voltage suppression across phase and neutral paths in low-voltage electrical distribution systems. Industrial installations utilize these combination units to mitigate the risk of direct lightning damage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • System configuration TN (EF009928): Yes
  • System configuration TN-C (EF009929): No
  • System configuration TN-C-S (EF009933): Yes
  • System configuration TN-S (EF009930): Yes
  • System configuration TT (EF009931): Yes
  • Number of poles (EF001391): 2
  • Lightning impulse current (10/350 µs) (EF000421): 12.5 kA
  • Max. continuous voltage AC (EF004198): 150 V
  • Nominal voltage AC (EF004220): 120 V
  • Voltage protection level (EF003525): 0.8 kV
  • Voltage protection level L-N (EF004236): 0.8 kV
  • Follow current extinguishing capability (EF004193): 0.1 kA
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Construction size (EF002566): 2 modular spacing
  • Signalling at the device (EF004241): Optic
  • Integrated backup fuse (EF008797): No

More info

▲
Lightning current combination arrestor, type 2

• For the equipotential bonding of lightning current to VDE 0185-305 (IEC 62305)
• Lightning current discharge capacity of 12.5 kA (10/350) per pole and up to 50 kA (10/350) in total
• Modular, plug-in arrestor with dynamic cut-off unit and visual status display
• Locking mechanism with vibration protection and voltage keying
• Halogen-free plastic (UL 94 V-0)
• The remote signalling (FS) variants have a potential-free changeover contact for remote signalling

Application: Lightning current equipotential bonding for buildings of class III and IV.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.