OBO BETTERMANN RJ45-TELE 4-F 5081984 OBO BETTERMANN DATA PROTECTION RJ45 S-ATM 8-F View larger
Images are for illustrative purposes only. Please refer to data sheet for details

5081984 OBO BETTERMANN DATA PROTECTION RJ45 S-ATM 8-F

RJ45-TELE 4-F

5081984

OBO BETTERMANN

1 Pcs.

DATA PROTECTION RJ45 S-ATM 8-F Fine protection device TELE 4-F for ISDN RJ45. Data line protection device for analogue telecommunications systems • In aluminium housing • With 2-stage protection circuit • Simple mounting• Incl. 150 mm connection cable with RJ11 and/or RJ45 connectors• Optimised bandwidth for TC systems• DIN rail mounting with DLS-BS accessories (5082 38 2)Application: For analogue telecommunication systems• In aluminium housing • Simple mounting on hat rail or on terminal• Incl. 150 mm connection cable with RJ411 connectors• Optimised bandwidth for telecommunications systems

Automation > Surge protection device for data networks/MCR-technology
TBS Transient and lightning protection systems - OBO BETTERMANN

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Data protection modules like the Obo Bettermann RJ45-TELE 4-F safeguard Ethernet network ports, telecommunication systems, and automated data logging hardware against lightning-induced surges and electrostatic interference. These specialized interface protectors maintain signal integrity while clamping dangerous transient voltages before they reach sensitive network electronics.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Capacity (wire-earth): <20 pF
  • Capacity (wire-wire): <500 pF
  • CO2 Footprint (GWP) Cradle-to-Gate: 1,8816 kg CO2e / 1 Piece
  • Cut-off frequency: 18 MHz
  • Dimension: 170V
  • Earthing via:: Connection cable
  • Impulse durability wire-earth: C2: 2 kV / 1 kA (8/20)
  • Impulse durability wire-wire: C1: 1 kV / 0,5 kA (8/20)
  • Insertion loss: ≤3 dB
  • Insulation resistance: > 34 MΩ
  • Kategorie: Type 2+3 / C2+C1
  • Lightning protection zone LPZ: 1→3
  • Maximum continuous voltage AC: 120 V
  • Maximum continuous voltage DC: 170 V
  • Nominal load current AC: 0,2 A
  • Nominal load current DC: 0,3 A

More info

▲
Capacity (wire-earth)<20 pF
Capacity (wire-wire)<500 pF
CO2 Footprint (GWP) Cradle-to-Gate1,8816 kg CO2e / 1 Piece
Cut-off frequency18 MHz
Dimension170V
Earthing via:Connection cable
Impulse durability wire-earthC2: 2 kV / 1 kA (8/20)
Impulse durability wire-wireC1: 1 kV / 0,5 kA (8/20)
Insertion loss≤3 dB
Insulation resistance> 34 MΩ
KategorieType 2+3 / C2+C1
Lightning protection zone LPZ1→3
Maximum continuous voltage AC120 V
Maximum continuous voltage DC170 V
Nominal load current AC0,2 A
Nominal load current DC0,3 A
Number of poles4
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemRJ45
Protection level wire-earth<600 V
Protection level wire-wire<300 V
Protection level, wire-earth at 1 kV/µs (C3)<245
Protection ratingIP40
Series resistance per wire2,2 Ω ± 10 %
Signalling on deviceWithout
SPD to IEC 61643-21Class II+III / C2+C1
Testing standardIEC 61643-21
Total discharge current (8/20)4 kA
Version forFine protection, 4 wires

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.