MURRELEKTRONIK 44275 44275 MURRELEKTRONIK FREQUENCY/VOLTAGE-CURRENT-CONVERTER View larger
Images are for illustrative purposes only. Please refer to data sheet for details

44275 MURRELEKTRONIK FREQUENCY/VOLTAGE-CURRENT-CONVERTER

44275

44275

MURRELEKTRONIK

1 unit


Automation > Relays, converters, switches
Relays, converters, switches

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Murrelektronik 44275 frequency/voltage-current-converter conditions frequency pulses into proportional standard analog signals for control instrumentation. Frequency converters enable tachometers and flow sensors to communicate with standard PLC analog inputs.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Operating voltage: 24 V DC ±20%
  • Operating current: max. 80 mA
  • Response time: max. 350 ms
  • Tolerance: 0.5% from end value
  • Test isolation voltage: 2.5 kV
  • Mounting method: DIN-rail mountable (EN 60715)
  • Temperature range: -25...+50 °C
  • Dimensions H×W×D: 90×12.4×70 mm
  • Input voltage: 10...30 V DC
  • Output signal: 0...10 V DC, 0...20 mA, 4...20 mA
  • Input current: 6...25 mA
  • Input resistor: approx. 1.2 kΩ
  • country of origin: CZ
  • customs tariff number: 85437090
  • EAN: 4048879028301
  • eClass: 27210990

More info

▲
INPUT: 0...1, 0...10, 0...100 kHz
OUTPUT: 0...10 V DC, 0...20 mA, 4...20 mA
Screw terminals
Input and output galvanically separated
Technical Data
Operating voltage24 V DC ±20%
Operating currentmax. 80 mA
Response timemax. 350 ms
Tolerance0.5% from end value
General data
Test isolation voltage2.5 kV
Mounting methodDIN-rail mountable (EN 60715)
Temperature range-25...+50 °C
Dimensions H×W×D90×12.4×70 mm
Description
Functional descriptionThe new frequency converter in the slim MIRO housing can be universally used. The frequency that is applied on the three inputs, will be galvanically isolated, transformed and is available as analog signal on all three outputs.
Voltage inputs
Input voltage10...30 V DC
Voltage output signals
Output signal0...10 V DC, 0...20 mA, 4...20 mA
Current input signals
Input current6...25 mA
Input resistorapprox. 1.2 kΩ
Commercial data
country of originCZ
customs tariff number85437090
EAN4048879028301
eClass27210990
Packaging unit1

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.