LOVATO ELECTRIC P1RB1NC06AC300 P1RB1NC06AC300 LOVATO RESIDUAL CURRENT CIRCUIT BREAKER WITH OVERCURRENT PROTECTION, 10KA. 2 MODULES, 1P+N TY.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

P1RB1NC06AC300 LOVATO RESIDUAL CURRENT CIRCUIT BREAKER WITH OVERCURRENT PROTECTION, 10KA. 2 MODULES, 1P+N TY..

P1RB1NC06AC300

10000

LOVATO ELECTRIC

1 Pcs.

RESIDUAL CURRENT CIRCUIT BREAKER WITH OVERCURRENT PROTECTION, 10KA. 2 MODULES, 1P+N - TYPE AC, 32A, 300mA RCBO 1P+N C 6A IDN 300MA 10KA Residual current circuit breaker with overcurrent protection, 10kA. 2 modules, 1P+N - type AC, 06A RESIDUAL CURRENT CIRCUIT BREAKER, 10KA. 2 MODULES, 1P+N TYPE AC, 6A, 300mA

Automation > Earth leakage circuit breaker
Miniature and residual circuit breakers

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The P1RB1NC06AC300 LOVATO RESIDUAL CURRENT CIRCUIT BREAKER WITH OVERCURRENT PROTECTION, 10KA. 2 MODULES, 1P+N TY.. functions as a combined protective device designed to guard electrical circuits against both overload currents and earth leakage faults. Such units are commonly installed in distribution boards to enhance personnel safety and prevent equipment damage in commercial and industrial settings.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Disconnection characteristic (EF012587): Undelayed
  • Degree of protection (IP) (EF005474): IP20
  • Frequency (EF005455): 50/60 Hz
  • Leakage current type (EF002560): AC
  • Release characteristic (EF000889): C
  • Voltage type (EF000187): AC
  • Ambient temperature during operating (EF007515): -25 °C
  • Connectable conductor cross section solid-core (EF007337): 1 mm²
  • Anti-nuisance tripping version (EF009497): No
  • With interlocking device (EF007385): No
  • Concurrently switching neutral conductor (EF005997): Yes
  • Rated impulse withstand voltage Uimp (EF011980): 4 kV
  • Number of poles (total) (EF008618): 2
  • Number of protected poles (EF005548): 1
  • Width in number of modular spacings (EF002950): 2
  • Pollution degree (EF002570): 2

More info

▲

P1RB1NC06AC300

Residual current circuit breaker with overcurrent protection, 10kA. 2 modules, 1P+N - type AC, 06A

Technical specifications

Type of product:
Residual current circuit breakers with overcurrent protection
Number of DIN modules:
2
Number of poles:
1P+N
Tripping curve:
C
Residual operation characteristic:
AC
Rated residual current I∆n [mA]:
300
Rated current In [A]:
6
Compliance:
IEC
Order codeP1RB1NC06AC300
Weight [g]205
Qty. per package1
Multiple qty. of packs per order1
Package dimensions [mm]115X040X080
Volume [cm³]368
Bar code [EAN13]8013975204399
HS Code85363010

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.