View larger
GE2500E
10000
LOVATO ELECTRIC
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Order code | GE2500E |
| Weight [g] | 11900 |
| Qty. per package | 1 |
| Multiple qty. of packs per order | 1 |
| Package dimensions [mm] | 700X710X900 |
| Volume [cm³] | 447300 |
| Bar code [EAN13] | 8013975245835 |
| HS Code | 85365080 |
| Product designation | Changeover switch | |||
| Product type designation | GE | |||
| Number of poles | Nr. | 3 | ||
| Operating voltage type | AC | |||
| Contact characteristics | ||||
| IEC Conventional free air thermal current Ith | A | 2500 | ||
| Rated insulation voltage Ui IEC/EN | V | 1000 | ||
| Rated impulse withstand voltage Uimp | kV | 8 | ||
| Operating current Ie | ||||
| AC21A | ||||
| 400V | A | 2500 | ||
| 500V | A | 2500 | ||
| 690V | A | 2500 | ||
| AC22A | ||||
| 400V | A | 2500 | ||
| 500V | A | 2000 | ||
| 690V | A | 1800 | ||
| AC23A | ||||
| 400V | A | 1800 | ||
| 500V | A | 1250 | ||
| 690V | A | 1000 | ||
| Power dissipation per pole max | W | 213 | ||
| Rated operational power AC23A | ||||
| 400V | kW | 956 | ||
| 690V | kW | 956 | ||
| Reactive power for control of capacitors at | ||||
| Rated short time current (1s) Icw (rms) | kA | 50 | ||
| Making capacity AC23A 400V | A | 18000 | ||
| Breaking capacity AC23A 400V | A | 14400 | ||
| Mechanical life | cycles | 600 | ||
| Mechanical features | ||||
| Operating position | ||||
| normal | Vertical plan | |||
| allowable | Any | |||
| Fixing | Screw | |||
| Terminals | ||||
| type | Bar | |||
| screw | M12 | |||
| Tightening torque for terminals | ||||
| max | Nm | 45 | ||
| Ambient conditions | ||||
| Operating temperature | ||||
| min | °C | -25 | ||
| max | °C | +55 | ||
| Storage temperature | ||||
| min | °C | -40 | ||
| max | °C | +70 | ||
| Max altitude | m | 3000 | ||
| ETIM classification | ||||
| ETIM 8.0 | EC000216 - Switch disconnector | |||
| Feature Name | Feature Value |
|---|---|
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Type of control element (EF006976) | Door coupling rotary drive |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Rated operating voltage (EF001435) | 400 V |
| Version as reversing switch (EF009408) | No |
| Voltage release optional (EF007491) | No |
| Motor drive optional (EF007386) | No |
| Suitable for distribution board installation (EF007262) | No |
| Suitable for front mounting 4-hole (EF007247) | No |
| Version as maintenance-/service switch (EF006986) | Yes |
| Version as safety switch (EF006985) | No |
| Version as main switch (EF006981) | Yes |
| Version as emergency stop installation (EF006959) | No |
| Motor drive integrated (EF006697) | No |
| Interlockable (EF006281) | No |
| Rated permanent current at AC-23, 400 V (EF011777) | 1800 A |
| Rated permanent current at AC-21, 400 V (EF009165) | 2500 A |
| Max. rated operation voltage Ue AC (EF007355) | 690 V |
| Rated short-time withstand current lcw (EF007050) | 50 kA |
| Rated operation power at AC-23, 400 V (EF007027) | 997 kW |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| Conditioned rated short-circuit current Iq (EF001444) | 100 kA |
| Number of poles (EF001391) | 3 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |