LEGRAND 423053 423053 LEGRAND DPX3250HP MAG+DIF 4P 100A 36KA View larger
Images are for illustrative purposes only. Please refer to data sheet for details

423053 LEGRAND DPX3250HP MAG+DIF 4P 100A 36KA

423053

423053

LEGRAND

1 Pcs.

DPX3250HP MAG+DIF 4P 100A 36KA DPX³ 250 HP 4 Pole 100A Thermal Magnetic MCCB with Earth Leakage Module 36kA DPX³ 250 HP molded case switch - circuit breaker dif - 4P - 36kA - 100A

Automation > Power circuit-breaker for trafo/generator/installation protection
DPX3 MOLDED BOX

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Legrand 423053 molded case circuit breaker safeguards electrical installations by interrupting dangerous overcurrent conditions and short circuits. This unit is commonly installed in commercial and light industrial panels to protect downstream equipment and wiring from electrical faults.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Degree of protection (IP) (EF005474): IP30
  • Adjustment range undelayed short-circuit release (EF007131): 500 A
  • Integrated earth fault protection (EF007296): Yes
  • With integrated under voltage release (EF001390): No
  • Suitable for DIN rail (top hat rail) mounting (EF007250): No
  • Device construction (EF008240): Built-in device fixed built-in technique
  • Number of poles (EF001391): 4
  • Type of electrical connection of main circuit (EF006819): Bolt connection
  • Overload release current setting (EF002336): 80 A
  • Motor drive integrated (EF006697): No
  • Type of control element (EF006976): Toggle
  • Rated permanent current Iu (EF001389): 100 A
  • With switched-off indicator (EF007006): Yes
  • Motor drive optional (EF007386): Yes
  • Position of connection for main current circuit (EF006671): Front
  • Rated voltage (EF003977): 230 V

More info

▲
Rated permanent current Iu100 A
Rated voltage230-690 V
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz36 kA
Overload release current setting80-100 A
Adjustment range undelayed short-circuit release500-1000 A
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionYes
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact3
With switched-off indicatorYes
With integrated under voltage releaseNo
Number of poles4
Position of connection for main current circuitFront side
Type of control elementWing knob
Complete device with protection unitYes
Motor drive integratedNo
Motor drive optionalYes
Degree of protection (IP)IP30
Width140 mm
Height165 mm
Depth112 mm
degree of impact strength (IK)Not applicable
Operating / setting temperature-5-70 °C
Storage temperature-25-85 °C
Voltage typeAC
Frequency50-60 Hz
Electric supplying directionNot applicable
Terminal marking indicationNo
ColourGrey
RAL-number7035
Halogen freeYes
Terminals capacity2.5-120 mm²
Cable nature for connectionFlexible or rigid
Label space/information surfaceNo

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.