View larger
417364 LEGRAND MPX 63H GUARDAMT 18-26A
417364
417364
LEGRAND
1 Pcs.
Automation > Motor protection circuit-breaker
MOTOR CIRCUIT BREAKERS
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
MPX 63H GUARDAMT 18-26A from Legrand, bearing part number 417364, functions as a specialized protective switch built to shield industrial electric motors from overcurrent, locked rotor conditions, and thermal overloads. Devices of this type are widely utilized in control panels to provide reliable circuit isolation and manual switching control for multi-phase loads.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Switch off technique (EF007007): Thermomagnetic
- Height (EF000040): 140 mm
- Type of control element (EF006976): Rotating button
- With thermal overload protection (EF006233): Yes
- Degree of protection (IP) (EF005474): IP20
- Rated operation power at AC-3, 230 V (EF007025): 5.5 kW
- With integrated auxiliary switch (EF001387): Yes
- Rated operation power at AC-3, 400 V (EF001364): 11 kW
- Phase failure sensitive (EF007400): No
- Rated permanent current Iu (EF001389): 26 A
- Adjustment range undelayed short-circuit release (EF007131): 338 A
- With integrated under voltage release (EF001390): Yes
- Device construction (EF008240): Built-in device fixed built-in technique
- Number of poles (EF001391): 3
- Rated operating voltage (EF001435): 220 V
- Depth (EF000049): 144.6 mm
More info
▲- Pack (number of units)1
- Volume (dm3)1.331
- Weight (g)1 008.00
- Adjustable thermal release
- Magnetic release 13 Ie max.
- High breaking capacity
- With rotary handle
- Fixing on rail or by screw
- 3-phase motor 400/415 V : 11 kW
- Thermal release adjustment range : 18 to 26 A
- Magnetic release operating current : 338 A
- 415 V breaking capacity Icu : 50 kA
- Conform to IEC 60947-1, IEC 60947-2, IEC 60947-4 ; class 10