View larger
411967 LEGRAND DX3 4/63/30 B DIFFERENTIAL
411967
411967
LEGRAND
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
TERTIARY CIRCUIT BREAKERS
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Functioning as a differential switch and protective device, this Legrand 411967 unit detects insulation faults and leakage currents to isolate electrical circuits safely. It is typically integrated into distribution enclosures to provide reliable ground fault protection for industrial systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Explosion-proof (EF004663): No
- Connectable conductor cross section solid-core (EF007337): 0.75 mm²
- Frequency (EF005455): 50 Hz
- Selective protection (EF002561): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Ambient temperature during operating (EF007515): -25 °C
- Degree of protection (IP) (EF005474): IP20
- Leakage current type (EF002560): B
- Voltage type (EF000187): AC
- Additional equipment possible (EF008148): Yes
- Mounting method (EF000003): DIN rail
- Surge current capacity (EF002564): 3 kA
- Number of poles (EF001391): 4
- Short-time delayed tripping (EF003604): Yes
- Rated fault current (EF002358): 0.03 A
- Rated impulse withstand voltage Uimp (EF011980): 4000 kV
More info
▲Product features
Protects people against indirect contacts.It provides protection against fire hazards due to a persistent ground fault current.
It can also be used to control and isolate the installation.