View larger
411237 LEGRAND MAGNET DIFFER DX3 4P 30mA C32
411237
411237
LEGRAND
1 Pcs.
Automation > Earth leakage circuit breaker
TERTIARY CIRCUIT BREAKERS
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A magnetic differential circuit breaker provides combined protection against short circuits, overloads, and differential earth currents in power distribution systems. Legrand part number 411237 ensures reliable fault disconnection for multi-phase electrical installations. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Frequency (EF005455): 50 Hz
- Degree of protection (IP) (EF005474): IP20
- Leakage current type (EF002560): A
- Voltage type (EF000187): AC
- Concurrently switching neutral conductor (EF005997): Yes
- Surge current capacity (EF002564): 0.25 kA
- Anti-nuisance tripping version (EF009497): No
- Rated fault current (EF002358): 0.03 A
- Number of protected poles (EF005548): 4
- Built-in depth (EF000218): 44 mm
- Number of poles (total) (EF008618): 4
- Pollution degree (EF002570): 2
- Width in number of modular spacings (EF002950): 4
- With interlocking device (EF007385): Yes
- Rated current (EF000227): 32 A
- Current limiting class (EF002568): 1
More info
▲- Pack (number of units)1
- Volume (dm3)0.701
- Weight (g)504.00
- 4-module RCBOs are compatible with prong-type and fork type supply busbars
- 7-module RCBOs are compatible with prong-type supply busbars only
- C curve
- Nominal rating In : 32 A
- Number of modules : 4
- Conform to IEC 61009-1, IEC 62423 (F type)
- Voltage independent tripping
- Breaking capacity:
- 6000 - IEC 61009-1 - 10 kA / IEC 60947-2 for single pole + neutral, 2 and 4-pole
- AC type : detect AC component faults
- A type : detect AC and DC component faults
- F type (High immunity) : detect AC and pulsating DC residual currents. Enhanced immunity to unwanted tripping in disturbed environments. Detection of high frequency fault currents
- Can be equipped with DX³ signalling and remote tripping auxiliaries and motorised controls