The 409341 LEGRAND MAGNET DX3 10/16kA C 4P 50A is a four-pole magnetic circuit breaker built to protect heavy-duty electrical networks from short-circuit events. Industrial facilities and large commercial distribution boards rely on these robust switching devices to maintain operational safety and equipment integrity.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Explosion-proof (EF004663): No
- Connectable conductor cross section solid-core (EF007337): 1.5 mm²
- Ambient temperature during operating (EF007515): -25 °C
- Degree of protection (IP) (EF005474): IP20
- Concurrently switching neutral conductor (EF005997): Yes
- Voltage type (EF000187): AC
- Additional equipment possible (EF008148): Yes
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Number of protected poles (EF005548): 4
- Frequency (EF000416): 50 Hz
- Built-in depth (EF000218): 44 mm
- Number of poles (total) (EF008618): 4
- Pollution degree (EF002570): 2
- Width in number of modular spacings (EF002950): 4
- Rated insulation voltage Ui (EF001366): 500 V
- Connectable conductor cross section multi-wired (EF007343): 1.5 mm²
More info
▲| Built-in depth | 44 mm |
|---|---|
| Release characteristic | C |
| Number of poles (total) | 4 |
| Number of protected poles | 4 |
| Rated current | 50 A |
| Rated voltage | 400 V |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V | 16 kA |
| Voltage type | AC |
| Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V | 10 kA |
| Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V | 32 kA |
| Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V | 16 kA |
| Frequency | 50-60 Hz |
| Current limiting class | 3 |
| Flush-mounted installation | Yes |
| Concurrently switching neutral conductor | Yes |
| Pollution degree | 2 |
| Additional equipment possible | Yes |
| Width in number of modular spacings | 4 |
|---|---|
| Degree of protection (IP) | IP20 |
| Ambient temperature during operating | -25-70 °C |
| Connectable conductor cross section multi-wired | 1.5-25 mm² |
| Connectable conductor cross section solid-core | 1.5-35 mm² |
| Explosion-proof | No |
| Width | 70.8 mm |
| Height | 94.8 mm |
| Depth | 77.8 mm |
| degree of impact strength (IK) | IK02 |
| Storage temperature | -40-70 °C |
| Electric supplying direction | By the top or bottom |
| Colour | Grey |
| RAL-number | 7035 |
| Halogen free | Yes |
| Connection type | Screwed terminal |
| Label space/information surface | Yes |
| Mounting method | DIN rail |