View larger
Images are for illustrative purposes only. Please refer to data sheet for details
409257 LEGRAND MAGNET DX3 10/16kA C 3P 32A
409257
409257
LEGRAND
1 Pcs.
MAGNET DX3 10/16kA C 3P 32A
DX³ 10000A 3 Pole 32A MCB C Curve 16kA
DX³ 10000/16kA Circuit Breaker - 3P - 400V~ - 32A - C curve
Automation > Miniature circuit breaker (MCB)
INDUSTRIAL CIRCUIT BREAKERS
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
409257 LEGRAND MAGNET DX3 10/16kA C 3P 32A created by Legrand serves as a modular circuit breaker designed to protect electrical lines from overcurrent events and short circuits within commercial and industrial facilities.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Explosion-proof (EF004663): No
- Connectable conductor cross section solid-core (EF007337): 1.5 mm²
- Ambient temperature during operating (EF007515): -25 °C
- Degree of protection (IP) (EF005474): IP20
- Concurrently switching neutral conductor (EF005997): No
- Voltage type (EF000187): AC
- Additional equipment possible (EF008148): Yes
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Number of protected poles (EF005548): 3
- Frequency (EF000416): 50 Hz
- Built-in depth (EF000218): 44 mm
- Number of poles (total) (EF008618): 3
- Pollution degree (EF002570): 2
- Width in number of modular spacings (EF002950): 3
- Rated insulation voltage Ui (EF001366): 500 V
- Connectable conductor cross section multi-wired (EF007343): 1.5 mm²
More info
▲
Conform to IEC 60898-1 Breaking capacity 10000 - IEC 60898-1 - 400 VA 16 kA - IEC 60947-2 - 400 VA Can be equipped with DX3 auxiliaries and accessories
| Built-in depth | 44 mm |
|---|---|
| Release characteristic | C |
| Number of poles (total) | 3 |
| Number of protected poles | 3 |
| Rated current | 32 A |
| Rated voltage | 400 V |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V | 16 kA |
| Voltage type | AC |
| Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V | 10 kA |
| Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V | 32 kA |
| Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V | 16 kA |
| Frequency | 50-60 Hz |
| Current limiting class | 3 |
| Flush-mounted installation | Yes |
| Concurrently switching neutral conductor | No |
| Pollution degree | 2 |
| Additional equipment possible | Yes |
| Width in number of modular spacings | 3 |
|---|---|
| Degree of protection (IP) | IP20 |
| Ambient temperature during operating | -25-70 °C |
| Connectable conductor cross section multi-wired | 1.5-25 mm² |
| Connectable conductor cross section solid-core | 1.5-35 mm² |
| Explosion-proof | No |
| Width | 53.1 mm |
| Height | 94.8 mm |
| Depth | 77.8 mm |
| degree of impact strength (IK) | IK02 |
| Storage temperature | -40-70 °C |
| Electric supplying direction | By the top or bottom |
| Colour | Grey |
| RAL-number | 7035 |
| Halogen free | Yes |
| Connection type | Screwed terminal |
| Label space/information surface | Yes |
| Mounting method | DIN rail |