LEGRAND 028803 028803 LEGRAND DMX3 UND PROTECTION MP6 LSI View larger
Images are for illustrative purposes only. Please refer to data sheet for details

028803 LEGRAND DMX3 UND PROTECTION MP6 LSI

028803

028803

LEGRAND

1 Pcs.

DMX3 UND PROTECTION MP6 LSI Electronic protection unit MP6 LSI - for DMX³ 6000 circuit breakers DMX³ Electronic Protection Unit - MP6 with Touch Screen - LSI

Automation > Tripping bloc for power circuit-breaker
OPEN FRAME AUTOMATION DMX3

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Legrand 028803 DMX3 UND PROTECTION MP6 LSI is a high-performance electronic trip unit applied within heavy industrial switchgear to monitor large electrical currents. Such devices provide precise tripping behavior to isolate faults swiftly and maintain safety across main power distribution lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Number of poles: 4
  • Overload release current setting: 252 A
  • Rated permanent current Iu: 6300 A
  • Short-circuit release function: Undelayed

More info

▲
  • Pack (number of units)1
  • Volume (dm3)2.066
  • Weight (g)1 500.00
Product characteristics
MP6 touch screen protection units
  • Measure and display instantaneous, maximum and average values of different electrical values and protection conditions
  • Fault signalling and log
LSI protection unit
  • Adjustment of: Isd, tsd, Ir, tr and Ii
General characteristics
Electronic protection units for DMX³ 2500, 4000 and 6300
  • DMX³ circuit breakers must be equipped with electronic protection units (to be ordered together for factory assembly) enabling very precise adjustments of the protection conditions, while maintaining total discrimination with downstream devices
  • All protection units are equipped with batteries for powering in case of mains fault or when the breaker is open or not connected

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.