Legrand manufactures the 028776 DMX3 2500 L EXTR 4POLOS 2500 withdrawable circuit-breaker, engineered for high-capacity electrical distribution and main switchboard protection. Systems integrators deploy these heavy-duty units to interrupt severe fault currents, manage large electrical loads, and ensure safe maintenance procedures in industrial plants.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Degree of protection (IP) (EF005474): IP30
- Adjustment range undelayed short-circuit release (EF007131): 5000 A
- Integrated earth fault protection (EF007296): Yes
- With integrated under voltage release (EF001390): Yes
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- Device construction (EF008240): Built-in device slide-in technique (withdrawable)
- Number of poles (EF001391): 4
- Overload release current setting (EF002336): 1000 A
- Motor drive integrated (EF006697): Yes
- Type of control element (EF006976): Push button
- Rated permanent current Iu (EF001389): 2500 A
- With switched-off indicator (EF007006): Yes
- Motor drive optional (EF007386): Yes
- Position of connection for main current circuit (EF006671): Back
- Rated voltage (EF003977): 230 V
- DIN rail (top hat rail) mounting optional (EF008904): No
More info
▲- Pack (number of units)1
- Volume (dm3)298.584
- Weight (g)169 000.00
- Supplied with:
- 4 auxiliary contacts: NO/NC
- draw-out base and kit
- flat rear terminals for connection with bars
- door sealing
- Breaking capacity Icu 100 kA (415 V~)
- Frame 4000
- 4P
- In : 2500 A
- Automatic air circuit breakers must be equipped with electronic protection unit, imperatively ordered together for factory assembly
- Please ask for DMX³ order form
- Conform to IEC 60947-2