View larger
4521015 H07V-K 1X95 BK LAPP H07V-K 1X95 BK
4521015
4521015
H07V-K 1X95 BK
LAPP
500 m.
Cables > Power cable less 1 kV, for permanent installation
Single cores
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Facilitate secure power routing in heavy industrial machinery using the Lapp 4521015 single core cable. Flexible fine-stranded hook-up wires simplify installation within compact terminal spaces while maintaining dependable electrical conductivity. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- CPR: Article number choice under www.lappkabel.com/cpr
- Spool: d1 = 18 mm; d2 = 200 mm; b = 85 mm
- Core insulation: Based on PVC
- OD ≤ 8 mm: 4 x OD*/2 x OD**
- 8 < OD ≤ 12 mm: 5 x OD*/3 x OD**
- OD > 12 mm: 6 x OD*/4 x OD**
- U0/U: 450/750 V
- Fixed installation: -40°C to +70°C
- ETIM 5.0 Class-ID: EC000993
- ETIM 5.0 Class-Description: Single core cable
- ETIM 6.0 Class-ID: EC000993
- ETIM 6.0 Class-Description: Single core cable
More info
▲H07V-K, HAR, power and control cable, PVC, 450/750V, wiring of devices and control cabinets, flame-retardant, class 5/ fine wire, fixed installation, ring/spool
- CPR: Article number choice under www.lappkabel.com/cpr
- <HAR>
Benefits
- Cables' <HAR>marking also stands for the international endorsement of national certification institutes' testing marks and certificates, e. g. <VDE><HAR>. The <HAR>marking is of special importance in case of goods traffic between European countries.
Application range
- Laying in tubes, exposed or buried in plaster, and in closed installation ducts
- For direct laying on racks, troughs and tubes only as potential equalisation conductor
Product features
- Flame-retardant according IEC 60332-1-2
- Spool: d1 = 18 mm; d2 = 200 mm; b = 85 mm
Norm references / Approvals
- <HAR> cable type certification acc. EN 50525-2-31
- No cable type certified core insulation colours according to EN 50525-1/ VDE 0285-525-1: transparent, green (single colour), yellow (single colour), all double colours (except of green-yellow and yellow-green)
Product Make-up
- Fine-wired copper conductor of bare copper strands in line with conductor class 5 acc. IEC 60228
- Core insulation: Based on PVC
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000993
- ETIM 5.0 Class-Description: Single core cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000993
- ETIM 6.0 Class-Description: Single core cable
Conductor stranding
- Fine wire according to VDE 0295 Class 5/ IEC 60228 Class 5
Minimum bending radius
- According to EN 50565-1
- OD ≤ 8 mm: 4 x OD*/2 x OD**;
8 < OD ≤ 12 mm: 5 x OD*/3 x OD**;
OD > 12 mm: 6 x OD*/4 x OD**
Nominal voltage
- U0/U: 450/750 V
Test voltage
- 2500 V
Current rating
- VDE 0298 Part 4
- EN 50565-1/ VDE 0298-565-1
Temperature range
- Fixed installation: -40°C to +70°C