LAPP 4520036 4520036 H07V-K 1X16 BN LAPP H07V-K 1X16 BN View larger
Images are for illustrative purposes only. Please refer to data sheet for details

4520036 H07V-K 1X16 BN LAPP H07V-K 1X16 BN

4520036

4520036

H07V-K 1X16 BN

LAPP

100 m.

H07V-K 1X16 BN H07V-K

Cables > Power cable less 1 kV, for permanent installation
Single cores

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Lapp 4520036 single core cable provides dependable power routing inside standard electrical enclosures and distribution boards. Panel builders utilize these flexible conductors for fixed wiring layouts in industrial and commercial building infrastructure.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • CPR: Article number choice under www.lappkabel.com/cpr
  • Spool: d1 = 18 mm
  • d2: 200 mm
  • b: 85 mm
  • Core insulation: Based on PVC
  • OD ≤ 8 mm: 4 x OD*/2 x OD**
  • 8 < OD ≤ 12 mm: 5 x OD*/3 x OD**
  • OD > 12 mm: 6 x OD*/4 x OD**
  • U0/U: 450/750 V
  • Fixed installation: -40QC to +70QC
  • ETIM 5.0 Class-ID: EC000993
  • ETIM 5.0 Class-Description: Single core cable
  • ETIM 6.0 Class-ID: EC000993
  • ETIM 6.0 Class-Description: Single core cable

More info

▲

H07V-K, HAR, power and control cable, PVC, 450/750V, wiring of devices and control cabinets, flame-retardant, class 5/ fine wire, fixed installation, ring/spool

  • CPR: Article number choice under www.lappkabel.com/cpr
  • <HAR>

Benefits

  • Cables' <HAR>marking also stands for the international endorsement of national certification institutes' testing marks and certificates, e. g. <VDE><HAR>. The <HAR>marking is of special importance in case of goods traffic between European countries.

Application range

  • Laying in tubes, exposed or buried in plaster, and in closed installation ducts
  • For direct laying on racks, troughs and tubes only as potential equalisation conductor

Product features

  • Flame-retardant according IEC 60332-1-2
  • Spool: d1 = 18 mm; d2 = 200 mm; b = 85 mm

Norm references / Approvals

  • <HAR> cable type certification acc. EN 50525-2-31
  • No cable type certified core insulation colours according to EN 50525-1/ VDE 0285-525-1: transparent, green (single colour), yellow (single colour), all double colours (except of green-yellow and yellow-green)

Product Make-up

  • Fine-wired copper conductor of bare copper strands in line with conductor class 5 acc. IEC 60228
  • Core insulation: Based on PVC

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC000993
  • ETIM 5.0 Class-Description: Single core cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC000993
  • ETIM 6.0 Class-Description: Single core cable

Conductor stranding

  • Fine wire according to VDE 0295 Class 5/ IEC 60228 Class 5

Minimum bending radius

  • According to EN 50565-1
  • OD ≤ 8 mm: 4 x OD*/2 x OD**;
    8 < OD ≤ 12 mm: 5 x OD*/3 x OD**;
    OD > 12 mm: 6 x OD*/4 x OD**

Nominal voltage

  • U0/U: 450/750 V

Test voltage

  • 2500 V

Current rating

  • VDE 0298 Part 4
  • EN 50565-1/ VDE 0298-565-1

Temperature range

  • Fixed installation: -40°C to +70°C

Product Datasheet