View larger
30017798 J-H(ST)H...BD 2x2x0,8 BMK LAPP J-H(ST)H...BD 2x2x0,8 BMK
30017798
30017798
J-H(ST)H...BD 2x2x0,8 BMK
LAPP
100 m.
Cables > Data and communication cable
UNITRONIC low frequency
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Safety and integrity during emergency situations define the Lapp 30017798 J-H(ST)H...BD 2x2x0,8 BMK fire alarm cable. Telecommunication and fire safety cables are specifically installed in commercial and industrial buildings to maintain critical emergency communication networks when hazards arise. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- K1: approx. 300 pF/100 m
- K9-12: approx. 100 pF/100 m
- Fixed installation: 8 x outer diameter
- Core/core: 800 V
- Core/screen: 800 V
- 0.6 mm: max. 130 ohm/km
- 0.8 mm: max. 73.2 ohm/km
- 0.6 mm: 0.28 mm²
- 0.8 mm: 0.50 mm²
- Occasional flexing temperature: -5°C to +50°C
- Fixed installation temperature: -30°C to +70°C
- ETIM 5.0 Class-ID: EC000829
- ETIM 5.0 Class-Description: Signal-/telecommunications cable
- ETIM 6.0 Class-ID: EC000829
- ETIM 6.0 Class-Description: Signal-/telecommunications cable
More info
▲(J)-H(ST)H...BD - red-sheathed, halogen-free, bundle-twisted fire alarm cable with static foil shielding for stationary use, for instance on or under plaster
Benefits
- Used to meet enhanced fire protection requirements concerning protection of people and high-value property
- Does not emit any toxic or corrosive gases in the event of fire and resists the spread of fire
- Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency, electromagnetic fields
- Decoupling of circuits by means of
twisted-pair (TP) design (crosstalk effects)
Application range
- This halogen-free, flame-retardant cable with static shielding is made for stationary use for telephone, data and signal transmission in subscriber stations and private branch exchange construction for telephone systems
- For fixed installation on and under plaster, in dry and damp rooms
Product features
- Flame retardant acc. to DIN VDE 0472-804/08.83, Test method C
- Halogen-free according to EN 50267-2-1/-2
Product Make-up
- Solid bare copper conductor
- Core insulation made of special halogen-free compound
- Cores twisted into star quads,
5 star quads are twisted into a bundle,
bundles stranded in layers - Foil wrapping,
static screening made of aluminium-laminated plastic film with copper drain wire - Outer sheath made of special halogen-free compound
Outer sheath colour: flame red (RAL 3000)
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000829
- ETIM 5.0 Class-Description: Signal-/telecommunications cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000829
- ETIM 6.0 Class-Description: Signal-/telecommunications cable
Core identification code
- according to VDE 0815,
refer to Appendix T10
Mutual capacitance
- max. 120 nF/km
Coupling
- K1: approx. 300 pF/100 m
- K9-12: approx. 100 pF/100 m
Minimum bending radius
- Fixed installation: 8 x outer diameter
Test voltage
- Core/core: 800 V
- Core/screen: 800 V
Loop resistance
- 0.6 mm: max. 130 ohm/km
- 0.8 mm: max. 73.2 ohm/km
Conductor cross-section
- 0.6 mm: 0.28 mm²
- 0.8 mm: 0.50 mm²
Temperature range
- Occasional flexing: -5°C to +50°C
- Fixed installation: -30°C to +70°C