LAPP 30016600 30016600 ÖLFLEX HEAT MC 1565 4X1,5 LAPP ÖLFLEX HEAT 1565 MC 4X1,5 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

30016600 ÖLFLEX HEAT MC 1565 4X1,5 LAPP ÖLFLEX HEAT 1565 MC 4X1,5

30016600

30016600

ÖLFLEX HEAT MC 1565 4X1,5

LAPP

100 m.

ÖLFLEX HEAT 1565 MC 4X1,5 ÖLFLEX® HEAT 1565 MC

Cables > Power cable less 1 kV, for moving application
ÖLFLEX HEAT Temperature measurement cables

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ÖLFLEX® HEAT 1565 MC - Glass fibre insulated power cable for use in blast furnaces, glassworks, motor construction etc. at ambient temperatures up to +400 °C (short term +1565°C)

  • Short-term: up to +1565 °C
  • For use in dry conditions

Benefits

  • Low conductor-resistance due to the nickel-plated copper conductors
  • Able to withstand temporary contact with molten metal or glass

Application range

  • Guarantees the circuit even in areas with extremely high ambient temperatures
  • Blast furnaces and coking plants
  • Refineries
  • Glassworks
  • Aluminium and steelworks

Product features

  • Flame-retardant
  • Halogen-free
  • Only suitable for use in dry conditions

Product Make-up

  • Fine-wire strand made of nickel-plated copper
  • MICA tape wrapping and impregnated glass fibre braiding
  • Cores twisted together
  • Outer sheath: MICA tape-wrapping, impregnated glass fibre braiding, red

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC001578
  • ETIM 5.0 Class-Description: Flexible cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC001578
  • ETIM 6.0 Class-Description: Flexible cable

Core identification code

  • 2-core cable:
    blue, brown
  • 4-core cable:
    black, blue, yellow, red

Conductor stranding

  • Fine copper wire strands

Minimum bending radius

  • Fixed installation:
    5 x cable diameter

Nominal voltage

  • U0/U: 300/500 V

Test voltage

  • 2200 V

Temperature range

  • -195°C to +400°C
  • Short-term: up to +1565 °C

Product Datasheet