LAPP 221407 221407 ÖLFLEX TRAY II 7G2,5 LAPP ÖLFLEX TRAY II 7G2.5 14/7C View larger
Images are for illustrative purposes only. Please refer to data sheet for details

221407 ÖLFLEX TRAY II 7G2,5 LAPP ÖLFLEX TRAY II 7G2.5 14/7C

221407

221407

ÖLFLEX TRAY II 7G2,5

LAPP

1 m.

ÖLFLEX TRAY II 7G2.5 14/7C ÖLFLEX® TRAY II

Cables > Power cable less 1 kV, for permanent installation
ÖLFLEX TRAY CABLE

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ÖLFLEX® TRAY II: UL TC-ER 600V or AWM 1000V, WET 75°C, SUN/ OIL RES I+II, DIR BUR, CSA AWM I/II A/B FT4, PVC power + control cable, 0.6/1 kV, Tray - Exposed Run

  • Torsion resistant for drip loops
  • Broad application range (NFPA 70/NEC), NFPA 79 compliance
  • Outdoor use in USA

Benefits

  • Cost-saving, fast installation omitting protection systems
  • Many certifications/ use types
  • 75 °C WET Rating + Sunlight Resistant Rating: Outdoor use in the USA

Application range

  • Industrial machinery, plant engineering in the USA
  • Unprotected 600V operation on cable tray in the USA, incl. 6 ft. Exposed Run laying sections for version with at least 3 conductors
  • Compliant with Tool machines: (UL) MTW
  • Outdoor use and Direct Burial in the USA, per UL 1277
  • USA Wind Turbine Tray Cable (WTTC) do turbin wiatrowych

Product features

  • Flame-retardant according to CSA FT4
    UL Vertical-Tray Flame Test
  • Oil-resistant according to UL OIL RES I & II
  • Water-resistant, UL 75°C WET rating
  • UV resistant (SUN RES), Ozone resistant
  • Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG)

Norm references / Approvals

  • USA: (UL) TC-ER [E171371], (UL) MTW [E155920], (UL) WTTC [E323700], Submersible Pump (14 - 2 AWG), (UL) PLTC-ER (18 - 12 AWG) [E216027], (UL) ITC-ER (18 - 12 AWG) [E196134], (UL) DP-1 [E233406], UL AWM (18 - 2 AWG) [E100338]
  • UL OIL RES I/ II, 75°C WET, 90°C DRY, SUN RES, DIR BUR, NEC/NFPA 70, NFPA 79
  • CAN: c(UL) CIC/ TC 600V FT4 (< 250 kcmil) [E171371], CSA AWM I/II A/B FT1

Product Make-up

  • Fine-wire strand made of bare copper wires
  • Insulation: PVC+nylon sheath (PA skin)
  • Outer jacket: Specially formulated thermoplastic polymer
  • Color of the outer jacket: Black

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC000104
  • ETIM 5.0 Class-Description: Control cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC000104
  • ETIM 6.0 Class-Description: Control cable

Core identification code

  • Black with white numbers

Conductor stranding

  • Fine copper wire strands

Torsion movement in WTG

  • TW-0 & TW-2, refer to Appendix T0

Minimum bending radius

  • 2 AWG (33.62 mm2) & smaller: 4 x OD
  • 1 AWG (42.41 mm2) & larger: 6 x OD

Nominal voltage

  • UL/CSA: 600 V (TC, MTW, CIC), WTTC 1000 V
  • UL/CSA: 1000 V (AWM)
    IEC: U0/U = 600/1000 V

Protective conductor

  • G = with GN-YE protective conductor
  • X = without protective conductor

Temperature range

  • -40°C (static)/ -25°C (occ. moved) to +90°C (TC) or +105°C (AWM)

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.