View larger
2170905 ETHERLINE FIRE Cat.5e PH120 4x2x23/1 AWG LAPP ETHERLINE FIRE Cat.5e PH120 4x2x23/1 AWG
2170905
2170905
ETHERLINE FIRE Cat.5e PH120 4x2x23/1 AWG
LAPP
100 m.
Cables > Data and communication cable
Etherline Industrial cabling
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Lapp 2170905 ETHERLINE FIRE Cat.5e PH120 4x2x23/1 AWG data cable is designed for critical data communication networks requiring circuit integrity and fire resistance in emergency situations. Such specialized cabling is deployed in safety systems, transport infrastructure, and industrial facilities with strict fire safety codes.
Specific pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Core insulation: Based on Polyolefin
- Twisting: 2 twisted-pair cores, stranding from 4 pairs
- Halogen-free and flame-retardant FRNC outer sheath, colour: red (similar to RAL3000)
- Fixed installation: 15 x outer diameter
- Fixed installation: -20°C to +70°C
- ETIM 5.0/6.0 Class-ID: EC000830
- ETIM 5.0/6.0 Class-Description: Data cable
- ETIM 6.0 Class-ID: EC000830
- ETIM 6.0 Class-Description: Data cable
More info
▲Industrial Ethernet cable for fixed installation, insulation integrity for 120 minutes, qualified for 1 GBit/s
insulation integrity for at least 120 minutes in the event of fire
Benefits
- Ensures that the cable can still transmit
data during and after a fire for 120 min
(according to EN50200) - High-quality, double screening ensures high transmission reliability in areas with electromagnetic interference
Application range
- In industrial areas that use fire as a tool
- Highly combustible or fire-prone areas
- for fixed installation
- For indoor use
Product features
- Fire behaviour:
- Halogen-free (IEC 60754-1 & EN50267-2-1)
- Flame-retardant (IEC 60332-1)
- Fire retardant (IEC 60332-3-24)
- Low smoke density (IEC 61034-2) - Circuit integrity for data cables PH120 (120 minutes) acc. to EN 50289-4-16
Product Make-up
- Solid bare copper conductor
- Core insulation: Based on Polyolefin
- each insulation will be wrapped with a special tape (anti-fire barrier)
- Twisting: 2 twisted-pair cores, stranding from 4 pairs
- Halogen-free and flame-retardant FRNC outer sheath, colour: red (similar to RAL3000)
Classification ETIM 5
- ETIM 5.0/6.0 Class-ID: EC000830
- ETIM 5.0/6.0 Class-Description: Data cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000830
- ETIM 6.0 Class-Description: Data cable
Peak operating voltage
- (not for power applications) 125 V
Minimum bending radius
- Fixed installation: 15 x outer diameter
Characteristic impedance
- nom. 100 Ω acc. to IEC 61156-5
Temperature range
- Fixed installation: -20°C to +70°C