View larger
1600811 H07ZZ-F 4G1,5 LAPP H07ZZ-F 4G1,5
1600811
1600811
H07ZZ-F 4G1,5
LAPP
1 m.
Cables > Power cable less 1 kV, for moving application
Rubber cables
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A flexible cable, specifically the Lapp 1600811 H07ZZ-F 4G1,5, is utilized for power transmission in building installations, machinery, and various industrial equipment where moderate mechanical stress is expected. These cables distribute electrical power safely across dynamic setups, commercial facilities, and automated plant networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Core insulation: rubber compound, halogen-free
- Outer sheath: rubber compound, halogen-free
- ETIM 5.0 Class-ID: EC001578
More info
▲H07ZZ-F, <HAR>, power and control cable, rubber, 450/750V, halogen-free, flame-retardant IEC 60332-3-24 bundle fire test, low smoke LS0H EN 61034-2
Halogen-free
Benefits
- Broad usages due to halogen-free materials
- According to VDE 0100-711, cables with low smoke emission are required in buildings for exhibitions, shows and stands without a fire alarm system
- Type-compliant versions <HAR>-certified with "<HAR>” testing and certification mark for accelerated granting of approvals if final application of cable is within the European CENELEC area
Application range
- Stage technology
- For mobile equipment and machines
- According to EN 50565-2: In dry, damp and wet rooms as well as for fixed installation e.g. on the plaster
- For buildings or industrial plants with a high density of people or valuable assets
Product features
- Low amount of corrosive gases in the event of fire
- Flame-retardant according to IEC 60332-1-2 and bundle flame test according to IEC 60332-3-24
- Low smokes/low smoke density in the event of fire according to IEC 61034
- Ozone-resistant acc. to EN 50363-6, EN 60811-403, EN 50396-8.1.3
Norm references / Approvals
- <HAR> H07ZZ-F cable type approval according to EN 50525-3-21
Product Make-up
- Conductor made of bare copper wires
- Core insulation: rubber compound, halogen-free
- Outer sheath: rubber compound, halogen-free
Classification ETIM 5
- ETIM 5.0 Class-ID: EC001578
- ETIM 5.0 Class-Description: Flexible cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC001578
- ETIM 6.0 Class-Description: Flexible cable
Core identification code
- Up to 5 cores: colour-coded according to VDE 0293-308, refer to Appendix T9
- From 6 cores: black with white numbers
Conductor stranding
- Fine wire according to VDE 0295 Class 5/ IEC 60228 Class 5
Minimum bending radius
- 4 to 8 x outer diameter (EN 50565-1)
Nominal voltage
- U0/U: 450/750 VAC
In protected and fixed installations:
U0/U: 600/1000 V
Test voltage
- 2500 V
Protective conductor
- G = with GN-YE protective conductor
- X = without protective conductor
Current rating
- VDE 0298 Part 4
- EN 50565-1/ VDE 0298-565-1
Temperature range
- Fixed installation: -40°C up to +90°C
- Occasionally moved: -5°C up to +90°C