LAPP 1591502 1591502 J-Y(ST)Y...LG 3X2X0,8 LAPP J-Y(ST)Y...LG 3X2X0,8 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1591502 J-Y(ST)Y...LG 3X2X0,8 LAPP J-Y(ST)Y...LG 3X2X0,8

1591502

1591502

J-Y(ST)Y...LG 3X2X0,8

LAPP

100 m.

J-Y(ST)Y...LG 3X2X0,8 J-Y(ST)Y...LG Indoor Cable

Cables > Data and communication cable
UNITRONIC low frequency

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

J-Y(ST)Y...LG indoor installation cable for telecommunication/ information processing, solid conductor/ stationary use, layered stranding, static foil, VDE 0815

Benefits

  • Indoor telephone cables transmit analogue or digital signals
  • Aluminium-laminated plastic foil static screen with tin-plated drain wire minimises the interference of high frequency, electromagnetic fields
  • Decoupling of circuits by means of
    twisted-pair (TP) design (crosstalk effects)

Application range

  • Connection cable for use in electronics and in measurement, control and signal applications
  • In news and communication applications, the following connections can be installed: telephone, telefax, telex, standard modems for postal services; burglar and fire alarm systems (cf. fire alarm cables); communication and paging systems; access control, time and data control systems
  • Can be used in dry and wet interiors for fixed installation on and under plaster

Product features

  • The 2-paired versions = star quad cable design
  • Flame-retardant according IEC 60332-1-2

Norm references / Approvals

  • In accordance with DIN VDE 0815type J-Y(ST)Y...LG

Product Make-up

  • Solid bare copper conductor
  • Core insulation made of PVC
  • Cores twisted in pairs,
    pairs twisted together,
    foil wrapping over cable core,
    static screen made of aluminium-laminated plastic film with copper drain wire
  • Outer sheath made of PVC
    Outer sheath colour: grey (similar to pebble grey/ RAL 7032)

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC000829
  • ETIM 5.0 Class-Description: Signal-/telecommunications cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC000829
  • ETIM 6.0 Class-Description: Signal-/telecommunications cable

Core identification code

  • according to VDE 0815,
    refer to Appendix T10

Coupling

  • (800 Hz): K1: 80% ≤ 300 pF/100m

Conductor cross-section in

  • 0.6 mm: 0.28 mm²
  • 0.8 mm: 0.50 mm²

Cable attenuation/attenuation

  • 0.6 mm: 1.7 dB/km
  • 0.8 mm: 1.1 dB/km

Minimum bending radius

  • Fixed installation: 10 x outer diameter

Test voltage

  • Core/core: 800 V
  • Core/screen: 800 V

Loop resistance

  • 0.6 mm: max. 130 ohm/km
  • 0.8 mm: max. 73.2 ohm/km

Temperature range

  • Occasional flexing: -5°C to +50°C
  • Fixed installation: -30°C to +70°C

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.