LAPP 1243000 1243000 ÖLFLEX HEAT 125 SC 1X50 GNYE LAPP ÖLFLEX HEAT 125 SC 1X50 GNYE View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1243000 ÖLFLEX HEAT 125 SC 1X50 GNYE LAPP ÖLFLEX HEAT 125 SC 1X50 GNYE

1243000

1243000

ÖLFLEX HEAT 125 SC 1X50 GNYE

LAPP

50 m.

ÖLFLEX HEAT 125 SC 1X50 GNYE ÖLFLEX® HEAT 125 SC

Cables > Power cable less 1 kV, for permanent installation
ÖLFLEX HEAT Temperature measurement cables

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ÖLFLEX® HEAT 125 C MC - halogen free single core with GL certificate, special fire performance, IEC 60332-3, suitable for +125°C

  • CPR: Article number choice under www.lappkabel.com/cpr
  • VDE-tested and -marked
  • Improved characteristics in the event of a fire

Benefits

  • For safety in areas with high density of people
  • Reduction of flame propagation, density and toxicity of smoke gases in event of fire
  • Minimises damage to buildings and equipment caused by the formation of toxic acid fumes in fires
  • Certified for maritime applications

Application range

  • For the wiring and connection of lighting, heating appliances, control cabinets, and distributors in mechanical and plant engineering
  • For installation in tubes, on, in and under plaster as well as in closed installation ducts
  • Coil winding, electromagnets, pumps, electrical systems
  • Heat treatment plants, pressure die casting, heating and cooling technology
  • Suitable for assembling cable harnesses and wiring during switch cabinet installation

Product features

  • Fire behaviour:
    - Flame-retardant (IEC 60332-1-2)
    - Halogen-free (IEC 60754-1)
    - No corrosive gases (IEC 60754-2)
    - Low smoke density (IEC 61034-2)
    - Low toxicity (EN 50305)
  • Extended fire behaviour:
    H05Z-K (0,5mm² up to 1,0mm²):
    see data sheet
    H07Z-K (≥ 1,5mm²):
    no fire propagation according to IEC 60332-3-24 respectively IEC 60332-3-25
  • Oil-resistant according to DIN EN 50290-2-22 (TM54)
  • Abrasion and notch-resistant
  • UV-resistant according to ISO 4892-2, method A, and ozone resistant acc. to EN 50396 resp. VDE 0473-396, method B

Norm references / Approvals

  • Type H05Z-K and H07Z-K according to EN 50525-3-41 with advanced features
  • DNV GL certificate no. TAE00003NF

Product Make-up

  • Fine-wire, tinned-copper conductor
  • Electron beam cross-linked polyolefin copolymer insulation

Classification ETIM 5

  • ETIM 5.0 Class-ID: EC000993
  • ETIM 5.0 Class-Description: Single core cable

Classification ETIM 6

  • ETIM 6.0 Class-ID: EC000993
  • ETIM 6.0 Class-Description: Single core cable

Conductor stranding

  • Fine wire acc. to VDE 0295, class 5 / IEC 60228 class 5 from 0.5 mm²

Minimum bending radius

  • Fixed installation: 4 x outer diameter

Nominal voltage

  • Up to 1.0mm² U0/U 300/500 V
    From 1.5mm² U0/U 450/750 V
  • 0.6/1kV from 1.5 mm² in the case of fixed and protected installation

Test voltage

  • 4000 V

Temperature range

  • Fixed installation: -55°C to +125°C
    Temporary (3.000h): up to +145°C

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.