View larger
1232655 ÖLFLEX HEAT 650 SC 1x4 LAPP ÖLFLEX HEAT 650 SC 1x4
1232655
1232655
ÖLFLEX HEAT 650 SC 1x4
LAPP
100 m.
Cables > Power cable less 1 kV, for permanent installation
ÖLFLEX HEAT Temperature measurement cables
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered as a durable Lapp single core cable, the 1232655 ÖLFLEX HEAT 650 SC 1x4 facilitates efficient electrical signal and power distribution in demanding manufacturing environments. General cabling infrastructure relies on single-conductor lines to interconnect control gear, switchboards, and heavy machinery safely.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Core insulation: glass fibre covering and impregnated glass fibre braids
- Fixed installation: 5 x outer diameter
- U0/U: 300/500 V
- Occasional flexing: -50°C to +650°C
- Fixed installation: -50°C to +700°C
- ETIM 5.0 Class-ID: EC000993
- ETIM 5.0 Class-Description: Single core cable
- ETIM 6.0 Class-ID: EC000993
- ETIM 6.0 Class-Description: Single core cable
More info
▲ÖLFLEX® HEAT 650 SC - Glass fibre insulated single core for use in blast furnaces, glassworks, motor construction etc. at ambient temperatures up to +650°C
For use in dry conditions
Benefits
- Suitable for areas where the installation temperature and ambient temperature is very high
- Good electrical conductivity due to nickel strand also at high temperatures
Application range
- Heating modules, electric heating devices, heat lockers
- Furnaces, electric ranges, night storage heater
- Heavy industry, iron and steel works, foundries, glass and ceramic processing, chemical industries
- Machinery, apparatus and power plant construction
Product features
- Flame-retardant
- Halogen-free
- Only suitable for use in dry conditions
- ÖLFLEX® HEAT 1565 SC is recommended if the peak temperature of the application may briefly go beyond 700°C
Product Make-up
- Strand made of nickel
- Core insulation: glass fibre covering and impregnated glass fibre braids
Classification ETIM 5
- ETIM 5.0 Class-ID: EC000993
- ETIM 5.0 Class-Description: Single core cable
Classification ETIM 6
- ETIM 6.0 Class-ID: EC000993
- ETIM 6.0 Class-Description: Single core cable
Conductor stranding
- Fine wire
- see data sheet
Minimum bending radius
- Fixed installation: 5 x outer diameter
Nominal voltage
- U0/U: 300/500 V
Test voltage
- 1800 V
Temperature range
- Occasional flexing: -50°C to +650°C
- Fixed installation: -50°C to +700°C